Heating cooling, Indoor & outdoor split geothermal comfort systems, Gt-gs & gt-s performance correction factors – Carrier GT-S User Manual

Page 19

Advertising
background image

Indoor & Outdoor Split

Geothermal Comfort Systems

Carrier Indoor & Outdoor Split Geothermal Heat Pumps - Rev.: 08/10/05

17

CFM = airfl ow, cubic feet/minute
EWT = entering

water

temperature,

˚F

GPM = water

fl ow in US gallons/minute

EAT = entering air temperature, Fahrenheit

(dry

bulb/wet

bulb)

HC

=

air

heating

capacity,

Mbtuh

TC = total cooling capacity, Mbtuh

SC = sensible cooling capacity, Mbtuh

KW = total power unit input, KiloWatts

HR = total heat of rejection, Mbtuh

HE = total heat of extraction, Mbtuh

HWC = Hot Water Generator (desuperheater)

capacity,

Mbtuh

WPD = Water coil pressure drop (psi & ft hd)
EER = Energy

Effi ciency Ratio

= BTU output/Watt input

COP = Coeffi cient of Performance

= BTU output/BTU input

LWT = leaving

water

temperature,

°F

LAT = leaving air temperature, °F

LC = latent cooling capacity, Mbtuh

S/T = sensible to total cooling ratio

LWT = EWT -

HE

GPM x 500

LAT = EAT +

HC

CFM x1.08

LWT = EWT +

HR

GPM x 500

LAT (DB) = EAT (DB) -

SC

CFM x1.08

LC = TC - SC

S/T =

SC

TC

Heating

Cooling

Heating Corrections

Cooling Corrections

Sens Clg Cap Multiplier - Entering DB

°F

Ent Air DB

°F

Htg Cap

Power

Heat of

Ext

Ent Air

WB

°F

Total Clg

Cap

70

75

80

80.6

85

90

95

Power

Heat of

Rej

60

1.019

0.896

1.054

60

0.881

0.943

1.067

1.192

1.240

*

*

*

0.983

0.899

65

1.010

0.948

1.028

65

0.940

0.797

0.952

1.106

1.125

1.261

*

*

0.991

0.949

68

1.004

0.980

1.011

66.2

0.976

0.693

0.868

1.043

1.063

1.217

*

*

0.997

0.980

70

1.000

1.000

1.000

67

1.000

0.624

0.812

1.000

1.023

1.188

1.343

1.352

1.000

1.000

75

0.997

1.059

0.979

70

1.012

0.697

0.820

0.835

0.944

1.067

1.257

1.002

1.010

80

0.993

1.118

0.957

75

1.024

0.637

0.658

0.817

0.983

1.159

1.005

1.019

Rev. 5/2/00M

*

Sensible capacity equals total capacity (no latent capacity) at conditions shown as "

*

"

ARI/ISO/ASHRAE 13256-1 uses entering air conditions of Clg- 80.6

°F DB/66.2°F WB and Htg- 68°F DB/59°F WB

GT-GS & GT-S Performance Correction Factors