Carrier AQUASNAP 30MPA User Manual

Page 10

Advertising
background image

10

3. Install the inside coupling half over the gasket and then

install the outer half. Connect with nuts and bolts. Tighten

the nuts equally on both sides. Ensure there is no gap be-

tween the two halves of the coupling.

4. Alternately tighten the nuts with a wrench to draw the

coupling halves together uniformly. The joint is now

complete.

30MPW UNITS — In order to minimize the water pressure

drop in the system, use as few bends as possible in the field

water piping, and run the lines as short as possible. Size the

water lines according to the available pump pressure (not neces-

sarily the connection size), especially on cooling tower applica-

tions. See Carrier System Design Manual, Part 3, Piping Design.

See Fig. 11 for condenser pressure drops.

Set water regulating valve, if installed, to maintain design

head pressure. Do not adjust to compensate for high head pres-

sures caused by fouled condensers, excess refrigerant, or the

presence of noncondensables. Due to changes in water temper-

ature, it may be necessary to adjust the valve seasonally. After

adjusting for design head pressure, shut unit down. The water

regulating valve should shut off the flow of water in a few min-

utes. If it does not, raise head pressure setting. Make sure that

the capillary tube from each water regulating valve is connect-

ed to the proper condenser access fitting.

Provide a means for draining the system in the winter (if not

used) and for maintenance.

Water leaving the condenser is under pressure and should

not be connected directly into sewer lines. Check local codes.
EVAPORATOR DESCRIPTION — All 30MP units use a

brazed-plate heat-exchanger type evaporator. The heat ex-

changer is constructed essentially the same as the brazed-plate

condenser used on 30MPW units. See 30MPW Condenser De-

scription section on page 7 for more details. Similar to the con-

denser, the evaporator can only be chemically cleaned. See Fig.

12 for evaporator pressure drops.
EVAPORATOR PIPING — Plan evaporator fluid piping for

minimum number of changes in elevation, and for the fewest

number of bends possible. Install manual or automatic vent

valve at high points in the line. Maintain system pressure by

using a pressure tank or a combination of relief and reducing

valves.

A strainer with a minimum of 40 mesh must be installed

within 10 ft of the evaporator fluid inlet to prevent debris from

clogging or damaging the heat exchanger. This strainer is re-

quired and is available as an accessory.

See Carrier System Design Manual, Part 3, Piping Design,

for chilled fluid piping details.

The evaporator fluid inlet and outlet connections are vict-

ualic. The fluid enters at the top connection and leaves at the

bottom connection. Procedures for making the connections are

the same as for the 30MPW condensers. See 30MPW Con-

denser section on page 7 for more details.

Run the pump for 10 minutes, then clean the strainer before

starting the unit.

An evaporator flow switch is standard on all units. This is a

thermal dispersion type switch that is installed in the evapora-

tor fluid outlet. The switch is set to open when the evaporator

fluid flow drops below the minimum set point.

For variable primary flow applications, it may be necessary

to adjust the flow switch set point to avoid nuisance trips. Con-

tact Carrier service engineering for the mthod needed to adjust

the switch.

See Table 1 for minimum flow rates and loop volume.
The thermistors used to sense entering and leaving fluid

temperature are factory-installed in the evaporator entering and

leaving fluid nozzles.
AIR SEPARATION — For proper system operation, it is

essential that water loops be installed with proper means to

manage air in the system. Free air in the system can cause

noise, reduce terminal output, stop flow, or even cause pump

failure due to pump cavitation. For closed systems, equipment

should be provided to eliminate all air from the system.

The amount of air that water can hold in solution depends

on the pressure and temperature of the water/air mixture. Air is

less soluble at higher temperatures and at lower pressures.

Therefore, separation can best be done at the point of highest

water temperature and lowest pressure. Typically, this point

would be on the suction side of the pump as the water is return-

ing from the system or terminals. Generally speaking, this is

the best place to install an air separator, if possible.

1. Install automatic air vents at all high points in the system.

(If the 30MP unit is located at the high point of the

system, a vent can be installed on the piping entering the

heat exchanger on the ¼-in. NPT female port.)

2. Install an air separator in the water loop, at the place

where the water is at higher temperatures and lower

pressures — usually in the chilled water return piping.

On a primary-secondary system, the highest temperature

water is normally in the secondary loop, close to the

decoupler. Preference should be given to that point on the

system (see Fig. 13). In-line or centrifugal air separators

are readily available in the field.

It may not be possible to install air separators at the place of

lowest pressure and highest temperature. In such cases, prefer-

ence should be given to the points of highest temperature. It is

important that pipe be sized correctly so that free air can be

moved to the point of separation. Generally, a water velocity of

at least 2 feet per second will keep free air entrained and

prevent it from forming air pockets.

Automatic vents should be installed at all physically elevat-

ed points in the system so that air can be eliminated during

system operation. Provision should also be made for manual

venting during the water loop fill. It is important that the

automatic vents be located in accessible locations for

maintenance purposes, and that they be located where they can

be prevented from freezing.

Fig. 10 — Install the Victualic Coupling

a30-1245

Advertising