Twin City HA / HAB Fiberglass Wall Mount Ventilators - IM-3100 User Manual

Ha/hab fiberglass wall mount ventilators, Im-3100, Receiving

Advertising
background image

Receiving

The HA/HAB ventilator is shipped in two parts:
1. Fan housing assembly complete with fiberglass inlet

venturi to the wheel and complete motor and drive

assembly.

2. Flanged extruded aluminum louver assembly.
Duct adapter and companion angles are shipped loose

if unit is for inline application.
Inspect cartons or crates carefully before signing a deliv-

ery receipt for the carrier. If any damage is apparent,

note it on the carrier’s receipt so that a claim can be

filed against the carrier through your usual channels.

Handle the units carefully while delivering to installation

location. Use ordinary care in unpacking the units. If the

units, when unpacked, appear to be damaged in a way

that could not be determined at the time of delivery,

notify the carrier that concealed damage has been dis-

covered and insist on inspection by the carrier. Obtain

a copy of carrier’s inspection report showing the con-

cealed damages so that a claim can be filed through

your usual channels.
Study the attached installation prints carefully. Inspect

the units carefully for identification marks, fan rotation

symbols, etc.

©1997 Twin City Fan Companies, Ltd.

Installation

Wall Application

1. Remove wood shipping supports from fan assembly

(see Figure 1).

2. Locate and provide hole in the wall

1

2

" larger than

the fan housing (see Figure 2). This will provide an

opening for the electrical wiring into the unit.

3. Anchor the box in the wall, keeping a minimum of

2

3

8

" between the outside wall and any part of the

box or the power assembly.

4. Fasten the flanged extruded louver to the exterior

wall.

Inline Application

1. Remove wood shipping supports from fan assembly

(see Figure 1).

2. Attach duct adapter and companion angles to unit

per Figure 3 with fasteners supplied.

3. Before anchoring the unit to the ductwork, check line

voltage and current characteristics outlined in previ-

ous section.

4. Fasten the flanged extruded louver to the exterior wall

wherever the outlet of the ductwork ends.

For easy maintenance of the ventilator inline, provide a

drop-out section between ductwork and duct adapter

(see Figure 3).

Check, Test & Start Procedure

WARNING

Electric shock hazard. Could cause severe injury or

death. Failure to bond the frame of this equipment

to the building electrical ground by use of the

grounding terminal provided or other acceptable

means may result in electrical shock. Disconnect

electric power before servicing equipment. Service to

be performed only by qualified personnel.

BEFORE START-UP: Disconnect power to this unit

before servicing the unit.
1. Check to verify that the wheel is free to rotate.
2. Verify that supply voltage on the line side of discon-

nect agrees with voltage on unit identification plate

and is within the utilization voltage range as indicated

in Table 1.

Table 1.

SYSTEM VOLTAGE/

UTILIZATION VOLTAGE

UNIT NAMEPLATE

MIN.

MAX.

115/60/1

104

127

208-230/60/1 or 208-230/60/3

187

253

230/60/1 or 230/60/3

207

253

277/60/1

249

305

200/60/3

180

220

380/60/3

342

418

460/60/3

414

506

575/60/3

517

633

110/50/1

99

121

220/50/1

198

242

380-415/50/3

342

456

440/50/3

396

484

IM-3100

August 2014

HA/HAB Fiberglass

Wall Mount Ventilators

INSTALLATION, OPERATION & MAINTENANCE MANUAL

Advertising