Overview
This procedure shows how to replace VT8000 Series Room Controllers which are already installed and set-up to communicate with a
front end Multi-purpose Manager (MPM) via Zigbee or BACnet.
Use the following table to compare default values with the current parameter configurations on the VT8300/VT8350 before replacing the
Room Controller. Navigate through the Network, Configuration, and Setpoints/Display pages in the Setup menu and note the current
configurations if they are different from the default ones. Also, verify you are replacing the Room Controller with the same model.
Object Name
Default Configurations
Current Configurations
before Replacement
1/2 Zigbee Network
COM Address
254
PAN ID
0
Channel
10
2/2 Zigbee others
Permit Join
on
1/2 BACnet Network
COM Address
254
Network Units
Imperial
Network Language
English
BACnet Baud Rate
Auto
1/7 Configuration
BI 1 / UI 16 Status
None
BI 2 / UI 17 Status
None
RUI 1 / UI 19 Status
None
Occupancy Command
Local occ.
2/7 Configuration
Auto Mode
Enabled
Fan Menu (Sequence)
On-Auto
Auto Fan Function
AS
Standby Mode
Abs
Standby Differential
2 °C ( 3 °F )
3/7 Configuration
Standby Time
0.5H
Unoccupied Time
0H
• When replacing an installed Room Controller, turn off the HVAC
system to prevent any damage by potentially incorrect default
settings on the new Room Controller.
• Electronic controls are static sensitive devices. Discharge
yourself correctly before handling and installing Room Controller.
• Use high caution when installing Room Controller as a short
circuit or incorrect wiring may cause permanent damage to
Room Controller or equipment.
• All VT8000
®
series Room Controllers controls are designed
for use as operating controls only and are not safety devices.
Tampering with the Device or unintended application of the
Device will result in a void of warranty.
Legend
All models
VT8350 only
Note: ZigBee settings only apply if a ZIgBee
module is installed in Room Controller.