Overview

This procedure shows how to replace VT8000 Series Room Controllers which are already installed and set-up to communicate with a
front end Multi-purpose Manager (MPM) via Zigbee or BACnet.

Use the following table to compare default values with the current parameter configurations on the VT8300/VT8350 before replacing the
Room Controller. Navigate through the Network, Configuration, and Setpoints/Display pages in the Setup menu and note the current
configurations if they are different from the default ones. Also, verify you are replacing the Room Controller with the same model.

Object Name

Default Configurations

Current Configurations

before Replacement

1/2 Zigbee Network

COM Address

254

PAN ID

0

Channel

10

2/2 Zigbee others

Permit Join

on

1/2 BACnet Network

COM Address

254

Network Units

Imperial

Network Language

English

BACnet Baud Rate

Auto

1/7 Configuration

BI 1 / UI 16 Status

None

BI 2 / UI 17 Status

None

RUI 1 / UI 19 Status

None

Occupancy Command

Local occ.

2/7 Configuration

Auto Mode

Enabled

Fan Menu (Sequence)

On-Auto

Auto Fan Function

AS

Standby Mode

Abs

Standby Differential

2 °C ( 3 °F )

3/7 Configuration

Standby Time

0.5H

Unoccupied Time

0H

• When replacing an installed Room Controller, turn off the HVAC

system to prevent any damage by potentially incorrect default
settings on the new Room Controller.

• Electronic controls are static sensitive devices. Discharge

yourself correctly before handling and installing Room Controller.

• Use high caution when installing Room Controller as a short

circuit or incorrect wiring may cause permanent damage to
Room Controller or equipment.

• All VT8000

®

series Room Controllers controls are designed

for use as operating controls only and are not safety devices.
Tampering with the Device or unintended application of the
Device will result in a void of warranty.