REmOTE SENSOR ACCESSORIES
Model no.
Description
S3010W1045
Wall mounted temperature sensor
S3020W1045
Wall mounted temperature sensor with override button and occupancy status LED
Note:
If one or multiple sensor(s) is/are connected into the RS terminal, the internal temperature sensor is automatically disabled. Dis-
connecting the sensor(s) in RS terminal will re-activate the internal sensor.
Remote mount temperature sensors inputs use 10K type 2 NTC thermistors.
Features:
• Each sensor can be configured for various averaging combinations
• Optional occupancy led
• Optional override key
Wiring example of single remote room sensor:
VT8600
Series Controller
1xS3020W1000
Remote wiring 1 sensor
S2-1= On, S2-2=On
S3010W1000
Remote wiring 1 sensor
S2-1= On, S2-2=On
SCom
RS
Aux
C
DI
OR
Dip switch setting for 1 sensor
S2-1= On, S2-2=On
SCom
RS
Common
UI 20 - RS
B0 1 - AUX
C (Common)
UI 16
UI 17
ON
1 2
or