DGC-500 HMI
2-3
Figure 2-2. DGC-500 Rear Panel HMI
Table 2-2. DGC-500 Rear Panel HMI Descriptions
Call-Out
Terminals
Description
A
P22
CHASSIS GND. This terminal provides the chassis ground
connection. The DGC-500 must be hard-wired to earth ground with
no smaller than 12 AWG copper wire.
B
P20 (+), P21 (–)
BATT. DGC-500 operating power is applied to these terminals. The
DGC-500 accepts a nominal input of 12 Vdc or 24 Vdc.
C
P35 (+), P37 (–)
P2, P3, P4
Contact Sensing Terminals
ESTOP. These terminals function as the Emergency Stop input.
Power is removed from all DGC-500 output relays when this input is
open.
PROG INPUT1, PROG INPUT2, PROG INPUT3. These three inputs
can be independently programmed to function as an auto transfer
switch input, single-phase override input, low coolant level input, fuel
leak detection input, battery charger failure input, or an auxiliary
input. The inputs accept normally-open contacts connected between
terminals P2 (PROG INPUT1), P3 (PROG INPUT2), or P4 (PROG
INPUT3) and terminal P21 (BATT –).