INSTALLATION INSTRUCTIONS

PART No. F145-0825

REPLACEMENT FLAME SENSORS

These Flame Sensors may be used for replacing the entire unit

on "Old Style" Flame Sensors, or for replacing the Cell
Assembly only on "New Style" Flame Sensors.

REPLACING "NEW STYLE" FLAME SENSORS

"NEW STYLE" FLAME SENSORS

Fig. 1

(Type 956-126)

Alternate

Type 956-128

(Type 956-133)

Fig. 3

Fig. 4 - New Style Flame Sensor.

(Type 956-128)

Fig. 2

NOTE: Select proper bracket for your application, if replacement is necessary

On "New Style" Flame Sensors (Fig. 1,2, or3),to replace
the Cell Assembly:

1. Shut off electric power. Disconnect Flame Sensor leads

from the primary control.

2. Loosen screws holding ignition transformer and swing away

transformer to gain access to Flame Sensor.

3. Do not disturb position of bracket shown in Fig. 4. Simply

r e m o v e d e f e c t i v e C e l l A s s e m b l y b y r o t a t i n g
counterclockwise.

4. Install new Cell Assembly by inserting end through notched

opening in bracket and rotating clockwise.

5. Reconnect leads of Flame Sensor to primary control, being

sure that leads are clear of blower wheel.

(Type 956-72)

CELL ASSEMBLY

6. Close ignition transformer, being sure Flame Sensor leads

are clear of cover. Restore electric power and check burner
for proper operation.

REPLACING "OLD STYLE" FLAME SENSORS

To replace any of the "Old Style" Flame Sensors shown in

Fig. 5, 6, or 7, shut off electric power and disconnect Flame

Sensor leads from primary control. Loosen screws holding

ignition transformer and swing away transformer. Then replace
Flame Sensor according to instructions A, B, or C, which

follow:

A. Scroll Plate-Mounted Flame Sensor (Fig. 5)

1. Remove and set aside Flame Sensor Mounting Screw.

2. Reach beneath Scroll Plate and remove (and discard) old

Flame Sensor.

3. Assemble new 956-126 Flame Sensor as shown in Fig. 1

4. Install new Flame Sensor in exact same location as old

Flame Sensor and tighten mounting screw securely.
Reconnect leads of Flame Sensor to primary control,
being sure that leads are clear of blower wheel.

Fig. 5 — Old Style Flame Sensor.

5. Close ignition transformer, being sure Flame Sensor

leads are clear of cover. Restore electric power and
check burner for proper operation.