Setting fan speeds – high / low, Ucted, Entral – Bonaire Touchpad User Manual
Page 49: Eating, Controls – installation / setup / commissioning
M
ULTI
-A
PPLIANCE
T
OUCH
P
AD
Controls – Installation / Setup / Commissioning
Ducted Gas Central Heating
S
ETTING
F
AN
SPEEDS
–
H
IGH
/
L
OW
There are 2 available fan speed setting options for ducted gas central heating as set out on the Fan Speed
Options Chart. Minimum fan speed should be set so that the heater does not go out on over temperature.
NOTE: fan speed settings should ONLY be set by a qualified installer or service technician
Fan Speed Options
Installer Maintenance
Parameter
Default Value
Range
Low Fan Speed
1
27
0 – 35
High Fan Speed
2
35
0 – 35
High Fan Speed – Dual Cycle AC
3
35
0 – 35
To enter into the installer maintenance to adjust minimum and maximum fans speeds, the following steps
must be followed.
Step 1
Ensure the control is in the OFF mode.
Step 2
A series of unseen icons must be pressed
1. Press and hold the ZONE 4 (1) icon
allowing for a triple BEEP followed by a
single BEEP.
2. In quick succession press the unseen
SETUP icons ENTER (2), REVIEW (3) &
CLOCK (4).
If successfully executed the clock area
will display tP:01.
3. If unsuccessful repeat 1 and 2 of STEP 2.
Step 3
Using the
to select H 01 or if
Dual Cycle cooling is fitted HC 01 from the
clock display area.
Step 4
Press ENTER. The display will now change to
1 27 or any other previous setting.
Step 5 Using
the
to select the
parameter to be changed. Press ENTER. The
heater will begin operation.
NOTE:-
Wait for the heater to be fully
functional before adjusting the fan speeds.
Step 6 Using the
to change the
value / fan speed setting. Press ENTER to
save the revised setting.
Step 7
To change the other fan speed parameter repeat Step 5 – 6.
Step 8
Press FINISH to exit.
Bonaire Control Systems
Page 49