3 Ducting, Controls and Condensate
3.1 Ducting connections
Refer to diagram 3.3.
• Atmosorb HRD 275: 4 x air duct connections ø 150 mm, or
alternative ø 160 mm and ø 180 mm
• Atmosorb HRD 350: 4 x air duct connections ø 180 mm, or
alternative ø 200 mm
3.2 Bypass(Optional)
Refer to diagram 3.2.
• Atmosorb HRD 275 and HRD 350: 4 x air duct connections
ø 150 mm, or alternative ø 160 mm and ø 180 mm.
1 Outside air
2 Exhaust air (from living room)
3 Fresh air (to living room)
4 Outgoing air (to outside)
FILTER
Diagram 3.2
VENTILATION FLAP
AIR INLET FROM
OUTSIDE
14881
1
4
2
3
Diagram 3.3
14878
Diagram 3.1
14879
3.3 Remote Control
• Control cable from the remote control to the unit is a 2-core
cable, with cross-section 0,75 mm
2
. Maximum cable length
300m.
The connection must comply with the current rules and
regulations.
3.4 Condensate Drain Trap
The condensate drain trap must be connected to the threaded
tube under the unit. Additionally, an odour trap is required in
the waste water system. For hygienic reasons, between the
drain traps an air gap of at least 20 mm must be provided.
• Condensed water drain G 3/4 connection for the condensate
drain trap.
• The attached condensed water drain trap is designed to
compensate pressure between the device and the installation
room, for that reason it must always be filled with clear water.
EXTERNAL AIR OUTLET
FRESH AIR OUTLET
(TO ROOM)
FAN
CIRCUIT BOARD
FAN EXHAUST
CONDENSATE DRAIN
OUTLET
3 STAGE SWITCH
CONNECTION
BYPASS CONNECTION
EXTERNAL AIR INLET
AIR EXHAUST
EXHAUST AIR FILTER
HEAT EXCHANGER
EXTERNAL AIR FILTER