Installation, 16 user information – Glow-worm Clearly Heat Pumps Envirosorb2 User Manual
Page 35
0020117819_00 - 01/11 - Glow-worm
- 33 -
Code function
Description
Setting
factory
setting
Modifiable
parameter
Min
Max
146
Configuration for
stopping the heat
pump if control by S1
contact input
1 = Immediate halt (as soon as contact S1 moves into the open position, the heat
pump stops).
2 = Gradual halt (as soon as contact S1 opens, the speed of the compressor
gradually reduces. This configuration is used to delay the shutdown of the
compressor after contact S1 switches to the open position and to limit the number
of compressor cycles per hour to 3.
1
2
2
Yes
147
Configuration of
the output between
terminal channels 5
and N
1 = Unit alarm
2 = Ambient temperature setting reached
1
2
1
Yes
148 limit exterior
temperature (T0)
This parameter defines the exterior temperature that is the functioning limit and where
the heat pump stops. In this configuration, only the booster heating functions. See the
chapter "Configuring the booster heating".
-20°C 65°C
-20°C
Yes
149
Choice of display in
the command unit's
temperature zone
1 = Ambient temperature
2 = Temperature of water leaving the installation
3 = Temperature of water returning to the installation
4 = Temperature of the cooling fluid in the plate to plate exchanger
5 = Compressor suction temperature
6 = Compressor discharge temperature
7 = Exterior temperature
1
7
1
Yes
150 Exterior temperature
bivalence point (T1)
This temperature defines the external temperature from which the power of the
heat pump alone is not sufficient to meet the needs of the installation. Below this
temperature, the booster heating and the heat pump can function together. See
the chapter "Configuring the booster heating".
30°C -20°C
0°C
Yes
151 Delays for switching
on booster heating
This parameter defines the period from which the booster heating is switched on
when: T0 < exterior T° < T1.
1
60
20
minutes
Yes
152 Differential stop/
start booster heating
This parameter defines the differential between the installation's water
temperature setting and the water temperature from which the booster heating
switches on when: T0 < exterior T° < T1.
1°C
20°C
5°C
Yes
153
Mode of activation
hot-water demand
contact S5
1 = Always active (demand for hot water is always met)
2 = Activated only in heating and cooling modes (demand for hot water is met only in
heating or cooling mode)
1
2
1
Yes
154 Booster heating
functioning
This parameter defines the functioning of the booster heating when: exterior T° < T0.
0 = Continuous functioning
1 = ON/OFF functioning depends on the ambient temperature.
In case of a thermostat fault, switch to mode 3.
2 = ON/OFF functioning depends on the installation's water temperature.
1
2
1
Yes
155 Functioning of main
circulator
This parameter defines the functioning mode for the main circulator for an external
temperature < T0 (code 148)
0 = Stopped
1 = ON/OFF cycle identical to the booster heating
2 = Continuous operation
0
2
1
Yes
156
Configuration of
the output between
terminals 12 and N
Configuration of the output (connection between terminal channels 12 and N)
0 = Not used
1 = ON/OFF cycle identical to the main pump The water pump works continuously
in case of demand for hot water.
2 = ON/OFF cycle identical to the main pump The pump is halted in case of demand
for hot water.
0
2
2
Yes
157 Functioning of the
additional circulator
This parameter defines the functioning mode for the additional circulator for an
external temperature < T0 (code 148)
0 = Stopped
1 = ON/OFF cycle identical to the booster heating
2 = Continuous operation
0
2
1
Yes
158
Differential on the
temperature setting
from the ambient air
This parameter defines the differential on the ambient temperature setting in the
case where the parameter 100 is configured to 4 (regulation with the command
unit used as the room thermostat).
+/-
0.2°C
+/-
1°C
+/- 0.3°C
No
- advise the user of the precautions necessary to prevent
damage to the system, appliance and the building;
- remind the user to service the appliance annually.
- The user shall not interfere with or adjust sealed components.
- All servicing must be carried out by a competent person
approved at the time by the Health and Safety Executive.
16 User information
At the end of the installation, the installer must:
- explain the operation of the appliance and its safety devices to
the user, if necessary provide a demonstration and answer any
questions;
- hand over to the user all the required documentation,
- fill in the documents where necessary;
INSTAllATION