GP‐TS‐50 

___________________________________________________________ 

 

2. Connect powercord hot 1 and hot 2 to powercord lugs HOT 1 BLK and
HOT 2 RED.

3. Connect the generator neutral(s) to generator lug labeled NEUTRAL
WHT.

4. Connect generator hot 1 and hot 2 to generator lugs HOT 1 BLK and HOT
2 RED.

5. Connect output to panel or other destination to the applicable “panel” lugs.
The bypass switch should be in the “off” position (marked “1”).

2.5.2 Installation Between Inverter and Alternating Source
(Configuration B)

For installation between an inverter (default) and another power supply (dominant),
such as the output from a prior powercord/ generator transfer switch, connect the
inverter neutral to “powercord’ lug labeled NEUTRAL WHT, and connect the
inverter hot to “powercord” lugs labeled HOT 1 BLK and HOT 2 RED. Connect the
alternate power supply neutral to “generator” lug NEUTRAL WHT.

Connect alternate power supply hot 1 and hot 2 to “generator” lugs HOT 1 BLK and
HOT 2 RED. Connect the output to applicable “panel” lugs. These connections will
allow any other supply to dominate the inverter, and the inverter output will pass
through the normally closed contacts of the switch. This allows the inverter to
operate only in the absence of the other power supplies, which is ideal for inverters.
Set the timer delay bypass switch of the inverter/alternate source transfer switch to
the ON position.

2.5.3 Installation In Hybrid System With TS-30 For Designated
Circuits (Configuration C)

Install the TS-50 on the line side of the main distribution panel as illustrated in
Configuration A. The TS-30 can be installed between inverter (default) and a
circuit panel supplied by the larger amp alternating power supply (dominant).
Connect the inverter to terminals 7 and 8, and connect the 30-amp branch circuit to
5 and 6.

Connect the designated circuit panel to the output terminals. The inverter will only
supply the load in the absence of the 50 amp power supply, in which case, only the
load designated to the 30 amp branch circuit is supplied. The timer delay bypass
switch on the TS-30 should be in the ON position.