2-6

MicroLogix™ 1200 Analog Combo Module (4Ch IN / 4Ch Out)



User’s Manual Pub. 0300247-01 Rev. C

Figure 2-4

Note: Use the pull loop on the connector to disconnect modules. Do not
pull on the ribbon cable.

!

Attention

EXPLOSION HAZARD

In Class I, Division 2 applications, the bus connector must be

fully seated and the bus connector cover must be snapped in
place.

In Class I, Division 2 applications, all modules must be

mounted in direct contact with each other as shown on page 2-
4. If DIN rail mounting is used, an end stop must be installed
ahead of the controller and after the last 1762 I/O module.

Section 2.6
Field Wiring
Connections

Consider the following when wiring your system:

General

 Power and input wiring must be in accordance with Class 1, Division 2 wiring

methods, Article 501-4(b) of the National Electric Code, NFPA 70, and in
accordance with the authority having jurisdiction.

 Input and output channels are not isolated from one another.
 Use Belden™ 8761, or equivalent, shielded wire.
 To ensure optimum accuracy, limit overall cable impedance by keeping a cable

as short as possible. Locate the module as close to input devices as the
application permits.

 Digital and analog power must be supplied by an Isolated Secondary Limited

Energy Low Voltage source.

Inputs

 If multiple power supplies are used with analog inputs, the power supply

commons must be connected.

 For a thermocouple, use the shielded, twisted-pair thermocouple extension lead

Advertising