Figure 2-4
Note: Use the pull loop on the connector to disconnect modules. Do not
pull on the ribbon cable.
!
Attention
EXPLOSION HAZARD
In Class I, Division 2 applications, the bus connector must be
fully seated and the bus connector cover must be snapped in
place.
In Class I, Division 2 applications, all modules must be
mounted in direct contact with each other as shown on page 2-
4. If DIN rail mounting is used, an end stop must be installed
ahead of the controller and after the last 1762 I/O module.
Section 2.6
Field Wiring
Connections
Consider the following when wiring your system:
General
Power and input wiring must be in accordance with Class 1, Division 2 wiring
methods, Article 501-4(b) of the National Electric Code, NFPA 70, and in
accordance with the authority having jurisdiction.
Input and output channels are not isolated from one another.
Use Belden™ 8761, or equivalent, shielded wire.
To ensure optimum accuracy, limit overall cable impedance by keeping a cable
as short as possible. Locate the module as close to input devices as the
application permits.
Digital and analog power must be supplied by an Isolated Secondary Limited
Energy Low Voltage source.
Inputs
If multiple power supplies are used with analog inputs, the power supply
commons must be connected.
For a thermocouple, use the shielded, twisted-pair thermocouple extension lead