Auxiliary Output Contact (K3)

Description: K3 relay uses the same driver circuitry

as the K1 relay, but has its own relay checking circuitry.

This means that you should never use the K3 relay in

series with the K1 relay unless you use K2 in another

stop circuit.
Usage: K3 has both N.O. and N.C. outputs off the

same common. This can be used in conjunction with

the standard output contacts. Never just use K3 by

itself or with K1.

N.O. contact is closed when the curtain is GREEN.
N.C. contact is open when the curtain is GREEN.

Cincinnati Interface

Description: Provided to allow an external device to

determine if the light curtain is still capable of shutting

down the safety control circuit. The Cincinnati Interface

allows an external device to override the light curtain,

initiate a RED condition, and open up the standard

output relay contacts.
Application: Cincinnati Press, PLC
Usage:
Type1:
The press interface provides 24VDC when it

wants the guard to de-energize (go RED). Connect this

press signal to Terminal #5 and Ground to Terminal #6.
Type 2: The press interface provides Ground when it

wants the guard t de-energize (go RED). Connect this

signal to Terminal #6 and attach nothing to Terminal #5.

You must install the jumper J8 (bottom board).
(see Installation Procedures, “Controller Module Setup”)

External Relay Check

Description: Allows the MicroGuard to monitor a pair

of external relays in series using the external relays

secondary set of DRY contacts,

provided that they are

N.C. and captive contacts. This captive or force-guided

contact will maintain the identical position as the primary

set of contacts on the external relays, except that the

secondary set of contacts are wired up to signal the

reverse of the primary. (i.e., primary are N.O., secondary

are N.C.) The circuit looks for both closure and opening

of the external relay contacts. This system is the only

safe External Relay Check.
Application: Monitoring external relay contacts for

shorts or opens.
Usage: Follow Figure 1 for wiring your external relays.

You must first activate this feature by using the spare

jumper and placing it across J19 labeled EXT (door

board).

This system requires that both N.C. relay

contacts be wired in series then back to the terminals

inside the Controller Module. Relay contacts must be

DRY contacts. Both external relay contacts must be

closed when the light curtain is RED within .25 sec or an

Figure 1: Wiring External Relays