Contemporary Control Systems BACnet Cube I/O BMT-AI8 User Manual

Analog input module bmt-ai8

Advertising
background image

1. Description

The BACnet MS/TP module with 8 individually configurable
resistance or voltage inputs is designed for local switching
operations. It is suitable to record resistance or voltage values of for
example passive and active temperature sensors electrical
ventilation or mixing valves, valve positions etc. The inputs are
universally configurable by standard object via a BACnet-Client.
Addressing of the module and baud rate setting are done with the
two address switches (x1 / x10) on the front. Possible settings are
addresses 00 to F9 and baud rates 9600 Bd, 19200 Bd, 38400 Bd,
57600, 76800 Bd and 115200 Bd.

Analog Input Module

BMT-AI8

11088213

7603/899299-03

2. Declaration of Conformity

The device was tested according to the applicable standards. Con-
formity was proofed. The declaration of conformity is available at
the manufacturer METZ CONNECT GmbH.

Notes Regarding Device Description

These instructions include indications for use and mounting of the
device. In case of questions that cannot be answered with these
instructions please consult supplier or manufacturer.
The indicated installation directions or rules are applicable to the
Federal Republic of Germany. If the device is used in other countries
it applies to the equipment installer or the user to meet the national
directions.

Safety Instructions

Keep the applicable directions for industrial safety and prevention
of accidents as well as the VDE rules.
Technicians and/or installers are informed that they have to
electrically discharge themselves as prescribed before installation or
maintenance of the devices.
Only qualified personnel shall do mounting and installation work
with the devices, see section “qualified personnel”.
The information of these instructions have to be read and under-
stood by every person using this device.

Symbols

Warning of dangerous electrical voltage

Danger

means that non-observance may cause risk of life,
grievous bodily harm or heavy material damage.

Qualified Personnel

Qualified personnel in the sense of these instructions are persons
who are well versed in the use and installation of such devices and
whose professional qualification meets the requirements of their
work.
This includes for example:

• Qualification to connect the device according to the VDE

specifications and the local regulations and a qualification to put
this device into operation, to power it down or to activate it by
respecting the internal directions.

• Knowledge of safety rules.

• Knowledge about application and use of the device within the

equipment system etc.

3. Technical Data

BACnet Interface

Protocoll

BACnet MS/TP

Transmission rate

9600 ... 115200 Bd

(factory setting 9600 Bd)

Cabling

RS485 two wire bus with voltage

equalizing cable in bus / line topology;

terminate with 120 Ohms

Supply

Operating voltage range

20 ... 28 V AC/DC (SELV)

Current consumption

65 mA (AC) / 25 mA (DC)

Relative duty cycle

100 %

Input

Resistance range

40 Ohms to 4 MOhms

Voltage input

0 ... 10 V DC

Resolution

10 mV

Error

about ±100 mV

Housing

Dimensions WxHxD

2.0 x 2.8 x 2.6 in. (50 x 70 x 65 mm)

Weight

104 g

Mounting position

any

Mounting

standard rail TH35 per IEC 60715

Mounting in series

the maximum quantity of modules

without space

connected in line is limited to 15 or

to a maximum power consumption of

2 Amps (AC or DC) per connection to

the power supply. For any similar

block of additional modules a

separate connection to the power

supply is mandatory.

Material
Housing

Polyamide 6.6 V0

Terminal blocks

Polyamide 6.6 V0

Cover plate

Polycarbonate

Type of protection
(IEC 60529)
Housing

IP40

Terminal blocks

IP20

Terminal blocks

Supply and bus
4 pole terminal block

max. AWG 16 (1.5 mm²) solid wire

max. AWG 18 (1.0 mm²) stranded wire

Wire diameter

min. 0.3 mm up to max. 1.4 mm

(terminal block and jumper plug are

included to each packing unit)

Module connection
Input/Output

max. AWG 12 (4.0 mm²) solid wire

max. AWG 14 (2.5 mm²) stranded wire

Wire diameter

min. 0.3 mm up to max 2.7 mm

Protective circuitry

polarity reversal protection of

operating voltage

polarity reversal protection of supply

and bus

Temperature range

Operation

-5 °C ... +55 °C

Storage

-20 °C ... +70 °C

Display

Operating and bus activity green LED
Error indication

red LED

5. Connection Diagram

8 C2 7 C2 6 C2 5 C2 S

BUS A-

BUS B+

A1
A2

A-

B+

A1
A2

A-

B+

GND

24 V AC/DC

1 C2 2 C2 3 C2 4 C2 S

4. Wiring Diagram

BUS A-

BUS B+

8

C2

7

C2

6

C2

A2 /GND

A1/+24 V

BACnet MS/TP
on RS-485

RISC - CPU

24

V

Outputs:

Voltage 15 V DC

or 24 V AC/DC
Inputs:

Voltage: 0-10 V

Resistance:

40 Ohm - 4MOhm

S
S

C2

4

C2

3

C2

2

C2
1
C2

5

METZ CONNECT GmbH
Im Tal 2 | 78176 Blumberg | Germany | Phone +49 7702 533-0 | Fax +49 7702 533-433
Mounting instruction see www.metz-connect.com