Flowserve NMD User Manual
Page 6
NMD, NMAD USER INSTRUCTIONS ENGLISH 71576436 - 11/09
Page 6 of 40
HAZARDOUS LIQUIDS
When the pump is handling hazardous liquids care
must be taken to avoid exposure to the liquid by
appropriate sitting of the pump, limiting personnel
access and by operator training. If the liquid is
flammable and/or explosive, strict safety procedures
must be applied.
Gland packing must not be used when pumping
hazardous liquids.
PREVENT EXCESSIVE EXTERNAL
PIPE LOAD
Do not use pump as a support for piping. Do not
mount expansion joints, unless allowed by
Flowserve in writing, so that their force, due to
internal pressure, acts on the pump flange.
ENSURE CORRECT LUBRICATION
(See section 5, Commissioning, startup, operation
and shutdown.)
START THE PUMP WITH OUTLET
VALVE PART OPENED
(Unless otherwise instructed at a specific point in the
User Instructions.)
This is recommended to minimize the risk of
overloading and damaging the pump motor at full or
zero flow. Pumps may be started with the valve
further open only on installations where this situation
cannot occur. Pump outlet valve shall may need to
be adjusted to comply with the duty following the
run-up process. (See section 5, Commissioning
start-up, operation and shutdown.)
NEVER RUN THE PUMP DRY
INLET VALVES TO BE FULLY OPEN
WHEN PUMP IS RUNNING
Running the pump at zero flow or below the
recommended minimum flow continuously will cause
damage to the seal.
DO NOT RUN THE PUMP AT
ABNORMALLY HIGH OR LOW FLOW RATES
Operating at a flow rate higher than normal or at a
flow rate with no backpressure on the pump may
overload the motor and cause cavitations. Low flow
rates may cause a reduction in pump/bearing life,
overheating of the pump, instability and
cavitations/vibration.
1.6.4 Products used in potentially explosive
atmospheres
The following instructions for pumps and pump
units when installed in potentially explosive
atmospheres must be followed to help ensure
explosion protection.
The terminology and procedures ensure that the
installed pump is in compliance with the European
Directive 94/9/EC, known as the ATEX Directive, which
is mandatory in Europe and may also be specified in
other countries. Where applicable, both electrical and
non-electrical equipment must meet the requirements
94/9/EC.
Even if the installation is in a region where ATEX is not
the applicable regulation, the general measures
described shall be followed to ensure safe operation.
The measures are explained under the headings of:
•
Avoiding excessive surface temperature.
•
Preventing build up of explosive mixtures.
•
Preventing the generation of sparks.
•
Preventing leakages.
•
Maintaining the pump to avoid hazard.
1.6.4.1 Scope of compliance
Use equipment only in the zone for which it is
appropriate. Always check that the driver, drive
coupling assembly, seal and pump equipment are
suitably rated and/or certified for the classification of
the specific atmosphere in which they are to be
installed.
Where Flowserve has supplied only the bare shaft
pump, the Ex rating applies only to the pump. The
party responsible for assembling the pump set shall
select the coupling, driver and any additional
equipment, with the necessary CE Declaration of
Conformity establishing it is suitable for the area in
which it is to be installed.
The output from a variable frequency drive (VFD) can
cause additional heating affects in the motor and so, for
pumps sets with a VFD, the ATEX Certification for the
motor must state that it is covers the situation where
electrical supply is from the VFD. This particular
requirement still applies even if the VFD is in a safe
area.