Flowserve 3400MD Digital Positioner User Manual
Page 8
Logix 3400MD Digital Positioner FCD LGENIM3404-08-AQ –5/15
8
Table 7: Hazardous Locations Information
ATEX
Flame Proof
FM07ATEX0005X
II 2 G
Ex d IIB+H2 T4/T6 Gb IP65
T4 Ta = -52˚C to +80˚C
T6 Ta = -52˚C to +60˚C
II 2 D
Ex tD A21 IP65 T95˚C Db
Ta = -52˚C to +55C
Intrinsically Safe
FM07ATEX0029X
II 1 G
Ex ia IIC T4/T6
T4 Ta = -40˚C to +80˚C
T6 Ta = -40˚C to +40˚C
Entity Parameters
Fisco Field Device
Vmax = 24V
Imax = 380mA
Pi = 5.32W
Ci = 3.3nF
Li = 1uH
North America (FM/CSA)
Explosion Proof
Class I, Div 1, Groups B,C,D T6
DIP Class II, III, Div 1 Groups E,F,G T6
T6 Ta = -40˚C to +60˚C (FM US)
T4 Ta = -55˚C to +80˚C (CSA)
T5 Ta = -55˚C to +60˚C (CSA)
Type 4/4X IP65
Class 1, Zone 1, AEx d IIB+H2 T6 (FM US)
T6 Ta = -40˚C to +60˚C (FM US)
Type 4/4X IP65
Class 1, Zone 1, Ex d IIB+H2 T4/T6 (CSA)
T4 Ta = -55˚C to +80˚C
T6 Ta = -55˚C to +60˚C
Type 4/4X IP65
Intrinsically Safe
Class I,II, III, Div 1, Groups A,B,C,D,E,F,G T4/T6
Class I, Zone 0, AExia IIC T4/T6 (FM US)
Class I, Zone 0, Ex ia IIC T4/T6 (CSA)
T4 (Ta = -40˚C to +80˚C)
T6 (Ta = -40˚C to +40˚C)
Type 4/4X IP65
Entity Parameters
Fisco Field Device
Vmax = 24V
Imax = 380mA
Pi = 5.32W
Ci = 3.3nF
Li = 1uH
InMetro
Explosion Proof
TÜV 12.0646
Ex d IIB+H2 T5 Gb IP65
Ta = -55˚C to +80˚C
Ex tb IIIC T95C Db IP65
Ta = -55C to +55C
Intrinsically Safe
TÜV 12.0605
Ex ia IIC T4 Ga IP65
T4 Ta = -40˚C to +60˚C
Entity Parameters
Fisco Field Device
Vmax = 24V
Imax = 380mA
Pi = 5.32W
Ci = 3.3nF
Li = 1uH
Special Conditions for Safe Use:
1. When used within a Zone 0 location, cast-aluminum (when Enclosure Option b = 0, 2, 3, 4,or 5) enclosures shall be installed in such manner as to prevent the possibility of sparks resulting from
friction or impact against the enclosure.
2. To prevent the risk of electrostatic sparking, the equipment’s mechanical pressure gauges shall be cleaned only with a damp cloth.
3. Using the box provided on the nameplate, the user shall permanently mark the protection type chosen for the specific installation. Once the type of protection has been marked it shall not be
changed.
4. Consult the manufacturer if dimensional information on the flameproof joints is necessary.
Gost
TR CU
Ex d IIB+H2 T4/T6 Gb IP65
Ex ia IIC T4/T6 Ga IP65
Ex nL nA IIC T6
T4 (Ta = -52˚C to +80˚C)
T6 (Ta = -52˚C to +60˚C)
Ex tb IIIC T95C Db IP65
IECEx
Explosion Proof
IECEx FMG 11.0002X
Ex d IIB+H2 T4/T6 Gb IP65
T4 Ta = -52˚C to +80˚C
T6 Ta = -52˚C to +60˚C
Ex tb IIIC T95C Db
Ta = -52C to +55C
Intrinsically Safe
IECEx FME 07.0001X
Ex ia IIC T4/T6 Ga IP65
T4 Ta = -40˚C to +80˚C
T6 Ta = -40˚C to +40˚C
Entity Parameters
Fisco Field Device
Vmax = 24V
Imax = 380mA
Pi = 5.32W
Ci = 3.3nF
Li = 1uH