Elevate Unit

Elevate unit per local clim ate and code requirem ents to

provide clearance above estim ated snowfall level and
ensure adequate drainage of unit. Use snow stand in
areas where prolonged freezing tem peratures are
encountered.

If conditions or local codes require the unit be attached

to pad or m ounting fram e, tie down bolts should be used
and fastened through knockouts provided in unit base pan.

Roof Top Installations

Mount on level platform or fram e 6 inches above roof

surface. Place unit above a load-bearing wall and isolate
unit and tubing set from structure. Arrange supporting
m em bers to adequately support unit and m inim ize
transm ission of vibration to building. Ensure roof structure
and anchoring m ethod is adequate for location. Consult
local codes governing rooftop applications.

Roof m ounted units exposed to winds above 5 m ph

m ay require wind baffles to achieve adequate defrost. A
sheet m etal baffle should be spaced 6-1/2" from the fall of
the coil. The height should cover the face of the coil and
the length should be 6" from the access panel.

NOTE: Unit m ust be level to within ± 2/ (± 3/8 in./ft) per

com pressor m anufacturer specifications.

Clearance Requirem ents

W hen installing, allow sufficient space for airflow

clearance, wiring, refrigerant piping, and service. For
proper airflow, quiet operation and m axim um efficiency.
Position so water, snow, or ice from roof or eaves cannot
fall directly on unit.

DO LOCATE THE UNIT:

!

W ith proper clearances on sides and top of unit

!

On a solid, level foundation or pad

!

To m inim ize refrigerant line lengths

DO NOT LOCATE THE UNIT:

!

On brick, concrete blocks or unstable surfaces

!

Near clothes dryer exhaust vents

!

Near sleeping area or near windows

!

Under eaves where water, snow or ice can fall
directly on the unit

!

with clearance less than 2 ft. from a second unit

!

with clearance less than 4 ft. on top of unit

Operating Am bient

T he m inim um outdoor operating am bient in cooling

m ode is 55/F, and the m axim um outdoor operating
am bient in cooling m ode is 125/F. The m axim um outdoor
operating am bient in heating m ode is 66/F.

Indoor Coil Piston Selection

The outdoor heat pum p section m ust be m atched to a

factory approved indoor section. It is m andatory that the
installer ensure that the correct piston is installed in the
indoor section. If necessary rem ove the existing piston and
replace it with the correct piston See indoor unit
instructions for details of changing the piston. Contact
your distributor for accessory piston kits.

Indoor (Cooling) Piston Size

The evaporator coil may use an expansion valve (TXV) in place of piston.

NOTE: If a TXV is installed a hard start kit is required on
all m odels with reciprocating com pressors. See spec
sheet for proper kit selection.

14 SEER Heat Pum p M odels
All 14 SEER heat pum p m odels are only rated with TXV on
the indoor side.

Refrigeration Line Sets

Use only refrigerant grade copper tubes. Split

system s m ay be installed with up to 50 feet of line set (no
m ore than 20 feet vertical) without special consideration
(see long line set guidelines).

Accum ulation of water and ice in base pan m ay
cause equipm ent dam age.

13 SEER Heat Pum p Indoor Piston Sizes

Unit Size

2HP13

4HP13

18

.055

.051

24

.063

.055

30

.068

.059

36

.076

.070

42

.076

.070

48

.082

.082

60

.098

.082

14 SEER Heat Pum p Indoor TXV

Unit Size

TXV Kit

18 thru 36

TXV3

42 thru 48

TXV5