Fire Ready Hood

Preparing the Install Location

Mounting Bracket - The mounting bracket and hood must be centered over the range. If the range is not in place,
the center marking should be relative to it’s final position. Refer to page 7 for bracket mounting points, rear access
holes and access points.

Ductwork - The ductwork and fittings used for outside venting (if applicable) must be carefully selected to ensure
that the static pressure is in line with the fan parameters. The table below displays maximum duct length allowed for
the various fan options.

Hood

Width

NFPA 101

Compliance

Fan Type

Venting

CFM

(at hood)

Duct Length

(maximum)

30 inches

No

Internal

Front (recirculating)

140

Not applicable

No

Internal

Rear Discharge

250

Not applicable

No

Inline Duct Fan

Vertical Duct

470

35 feet

No

Exterior Wall Fan

Vertical Duct

150

20 feet

Yes

Internal

Front (recirculating)

500

Not applicable

Yes

Internal

Rear Discharge

500

Not applicable

Yes

Inline Duct Fan

Vertical Duct

510

35 feet

Yes

Exterior Wall Fan

Vertical Duct

550

20 feet

36 inches

No

Internal

Front (recirculating)

140

Not applicable

No

Internal

Rear Discharge

250

Not applicable

No

Inline Duct Fan

Vertical Duct

470

35 feet

No

Exterior Wall Fan

Vertical Duct

150

20 feet

Yes

Internal

Front (recirculating)

500

Not applicable

Yes

Internal

Rear Discharge

500

Not applicable

Yes

Inline Duct Fan

Vertical Duct

510

35 feet

Yes

Exterior Wall Fan

Vertical Duct

550

20 feet

Maximum duct length equals horizontal and vertical duct runs plus duct components such as fittings, elbows, and transitions.

For installations requiring vertical duct venting to an inline fan and NFPA 101 compliance, the hood should be
adapted from a 7-inch round duct access hole to a minimum 12-inch duct.

For installations requiring vertical duct venting to an inline fan and NFPA 101 compliance is NOT required, the hood
can be adapted to a minimum 10-inch duct.

WARNING

The amount of fittings and ductwork directly affects the resistance or static pressure placed on the system. If the
system is not within the proper static pressure range, the heat sensors and controls will be adversely affected and
will impact the proper function of the safety controls. Therefore it is required that airflow testing be recorded along
with installation documentation. The air testing is accessed by the removal of the grease tray and measured with
an airflow pressure gauge.

Static Pressure Testing - The magnehelic gauge test port opening is located
beneath the grease tray. The static pressure needs to be measured to ensure
airflows meet design criteria. The airflow is measured by attaching the gauge
tubing to the magnehelic gauge inlet, and the hood fitting is attached to the
grease drain hole beneath the grease tray.

A reading of 0.45 to 0.85 inches wg. is required to meet design standards.
This reading will correspond to the static pressure of the ductwork, hood
and fan combination.

Magnehelic Gauge
Test Port

Magnehelic Gauge
Test Port

®