Installation, Discharge positions – Greenheck SFD, SFB, SWB and SWD (455308) User Manual
Page 4
Centrifugal Utility Fans
4
®
Installation
Inspect the unit for any damage and report it to
the shipper immediately. Also, check to see that all
accessory items are accounted for.
Move the fan to the desired location and fasten
securely through mounting holes provided in the base
angles. The unit must be set level (shimming may be
necessary). Flexible duct connections and vibration
isolators should be used where noise is a factor.
The motor voltage and ampere rating must be
checked for compatibility with the electrical supply
prior to final electrical connection. Supply wiring to the
fan must be properly fused, and conform to local and
national electrical codes.
The discharge is factory set as specified by customer
order, however, it can be rotated to other discharge
positions in the field if necessary. Removal of the
housing bolts allows the discharge to be rotated to
the clockwise positions below. For TAD, BD and BAD
discharge positions, a portion of the frame angle must
be removed.
Clockwise rotation shown. Counterclockwise
discharge positions are a mirror image of those
shown. Fan rotation is always specified from the drive
side of the housing.
CW BH
CW BAU
CW TAU
CW UB
CW TH
CW TAD
CW BAD
CW DB
Discharge Positions
Installation of UL/cUL 762 Listed
Fans for Restaurant Exhaust
The UL/cUL 762 listing for restaurant exhaust is
available on model SWB Series 200, sizes 206 - 224,
and Series 300, sizes 327 - 349 with a weatherhood.
UL/cUL 762 fans are listed for a maximum operating
temperature of 375°F (191°C) and includes an access
door and 1 inch (25.4 mm) drain connection. An
outlet guard is strongly recommended when the fan
discharge is accessible. An upblast discharge is
recommended. The fan discharge must be a minimum
of 40 inches (1016 mm) above the roof line and the
exhaust duct must be fully welded to a distance of
18 inches (457 mm) above the roof surface.
40 in.**
(1016 mm)
18 in.*
(457 mm)
Duct
from
kitchen
hood
Upblast Discharge
Optional Companion
Flange
3 Wheel
Diameters
Weatherhood
**Per NFPA 96 the fan discharge must
be a minimum of 40 in. (1016 mm)
above the roof surface.
*Per NFPA 96 the duct
must be of all-welded
construction to a
minimum distance of
18 inches (457 mm)
above the roof surface.
SWB Series 200 and 300 models are
listed for grease removal (UL/cUL 762)
File no. MH11745
This drawing is for dimensional information only. See the latest edition
of NFPA 96 Standard for Ventilation Control and Fire Protection of
Commercial Cooking Operations for detailed installation instructions,
materials, duct connections and clearances.