INSTALLING DAMPER CLAMP

Secure the damper stop clamp provided to the leading

edge of the damper as shown in Figure 3. If for any rea-

son this clamp doesn't work on your fireplace, another

suitable clamp or permanent stop must be installed, or

the damper blade must be cut or removed.

Damper
Clamp

Damper
Clamp

Damper

Manufactured

Fireplace

Masonry Fireplace

Figure 3 - Attaching Damper Clamp

INSTALLATION

Continued

Damper

CONNECTING TO GAS SUPPLY

WARNING: A qualified service

person must connect log set to gas

supply. Follow all local codes.

Installation Items Needed
Before installing log set, make sure you have the

items listed below.
• piping (check local codes)
• sealant (resistant to Propane/LP gas)
• equipment shutoff valve
• test gauge connection
• adjustable (crescent) wrench or pliers
• sediment trap
• tee joint
• pipe wrench

CAUTION: Use only new, black

iron or steel pipe. Internally-tinned

copper tubing may be used in

certain areas. Check your local

codes. Use pipe of 1/2" diameter

or greater to allow proper gas vol-

ume to log set. If pipe is too small,

undue loss of volume will occur.

Installation must include an equipment shutoff

valve, union, and plugged 1/8" NPT tap. Locate

NPT tap within reach for test gauge hook up. NPT

tap must be upstream from log set (see Figure 4).
IMPORTANT:

Install equipment shutoff valve

in an accessible location. The equipment shutoff

valve is for turning on or shutting off the gas to

the appliance.
Apply pipe joint sealant lightly to male NPT

threads. This will prevent excess sealant from

going into pipe. Excess sealant in pipe could result

in a clogged burner injector.

WARNING: Use pipe joint

sealant that is resistant to liquid

petroleum (LP) gas.

We recommend that you install a sediment trap in

supply line as shown in Figure 4. Locate sediment

trap where it is within reach for cleaning. Install in

piping system between fuel supply and appliance.

Locate sediment trap where trapped matter is not

likely to freeze. A sediment trap traps moisture and

contaminants. This keeps them from going into log

set controls. If sediment trap is not installed or is

installed wrong, log set may not run properly.

Figure 4 - Gas Connection

* Purchase the optional CSA design-certified

equipment shutoff valve from your dealer. See

Accessories

, page 13.

** Minimum inlet pressure for purpose of input

adjustment.

3" Minimum

Sediment Trap

From Gas Meter
(5" W.C.** to
10.5" W.C.
Pressure)

CSA Design-Certified
Equipment Shutoff Valve
With 1/8" NPT Tap*

Approved Flexible Gas Hose
(if allowed by local codes)

Tee
Joint

Pipe
Nipple

Cap