Cm12: installation check sheet, Troubleshooting (cont.) – MovinCool CM12 User Manual

Page 20

Advertising
background image

20

TROUBLESHOOTING (cont.)

CM12: Installation Check Sheet

ITEMS

Installation

Unit

Check and make sure all screws are tight and

unit is secured in place.

Check and make sure inlet / outlet air exhaust

are clear without blockage.

Wiring

Check and make sure the unit is properly

connected to the dedicated circuit breaker.

Check and make sure all wiring are properly

connected and secured.

Check and make sure ground wire is tighten

and secured.

DIP Switch Setting

Check and make sure all DIP switches

located on relay board are set to “OFF”

positions.

Drain Hose

Connection

Check and make sure that drain hose

provided with heat insulator to prevent

condensation on hose surface.

Grill Installation

Check and make sure that grill is secured and

properly installed.

Wall Thermostat

Check and make sure wall thermostat is

connected properly to unit.

Other

Remove card board on condenser inlet side.

Before Test

Operation

Maintenance Switch Check and make sure override switch located

below maintenance’s panel is at “OPERATE”

position before test operation.

Test

Operation

Check Operation

with Wall

Thermostat

Set wall termostat to Fan On or Fan Only

mode to confirm fan only mode operation.

Set wall thermostat to Fan Auto or Cool mode

operation. During cool mode operation, check

and cinfirm cooling operation after delay timer

is expired. (Note: Delay timer vary from 2 ~ 5

min depending on thermostat model used.)

Abnormal Noise

Check and observe abnormal noise during

Blowing/Cooling operation.

Drain

During cooling operation, check and observe

condensation drip through normal drainage

path.

Air Leakage

Check for air leakage from duct and duct

connection.