INSTALLATION (cont.)

Fire Alarm Control Panel Connection

(Input Signal Terminal E+ and E-)

The controller is equipped with a normal open input signal, which can be

connected directly from the fire alarm control panel. This input signal terminal

should only be connected to a close or open dry contact signal. When receiving

the signal from the fire alarm control panel, the unit turns off and does not turn back

on until it has been RESET.

Connecting Fire Alarm Control Panel to Controller

1. Remove service panel from the rear of the unit.

2. Squeeze the inner latches and push out the black cap from inside the panel.

3. Use recommended warning signal wire size from 16 AWG to 26 AWG for a

solid wire, or 16 AWG to 22 AWG for a stranded wire with ring terminal for #6

stud size.

4. Connect warning device to terminal E+ and E- according to its polarities.

Cap

Latch

Input

Signal

Terminals

Output

Signal

Terminals