8.8 Full Drain Switch Inspection

• Depress the full drain switch to check for

continuity. If there is no continuity, replace the

switch.

• Normally: Continuity across 1 and 2.

• Switch Depressed: Continuity across 1 and 3.

I001745

Full Drain Switch

Relay
Board
(CN16)

1

2

3

NC

COM

NO

C (1)

NC (2)

8.9 Thermistor Inspection

• Use an ohmmeter to check the resistance

across the 2-pin connector at normal

temperature (77 °F (25 °C)).

8.10 Wiring Connection Inspection

• Refer to the wiring diagram on page 17 to 18, and check the connection of each wire.

CAUTION

Secure the wires using clamps to prevent contact with the edges of the structure, etc. Secure the

wires in the same position as prior to removal.

Type

Specification

Characteristic

Room Thermistor (RTS)

5 k ohm at 77 °F (25 °C)

Freeze Protection Thermistor

(CTS)

5 k ohm at 77 °F (25 °C)