Electrical system, 1 circuit diagram, Circuit diagram – MovinCool Classic 40 Service Manual User Manual
Page 22: Sw1 cool on/off switch
Operation Section
22
5. ELECTRICAL SYSTEM
5.1 Circuit Diagram
I003091
SW1
COOL ON/OFF Switch
Control Board
DIG
SW2
FAN Switch
SW3
SET TEMP Switch
SW4
SET TEMP Switch
SW1
CN8
SW2
SW3
SW4
4
5
3
2
1
CN9
R101
R102
R103
R104
R109
R110
R112
R111
LED1
LED2
LED4
LED3
R105
R106
R107
10
11
9
8
7
4
5
6
3
2
1
R108
R
S
T
CN03
MF2
1
3
5
CN16
1
TB3
5
(G)
2
4
6
(95)
External
Controller
G Y
AP
RC
TB1
RPHR
(R)
CN1
MCC
OCF1
OCF2
TB4
3
1
Fire Alarm
Input
On Board
Controller
OCF2
(U22)
(97)
1
3
1
2
2
1
3
1
(V22)
HPRS
CN3
1
11
5
1
5
1
13
23
33
11
TB2
E+
E-
L+
L-
R
CB
MCF
MCC
MF1
MC
MCF
S
T
1
(S)
AC220 V, 3 Phase, 60 Hz
(T)
(U11)
14
24
34
1
3
5
2
4
6
1
1
3
5
2
4
6
G
1
A2
A1
A1
A2
52ID
(V11)
OCF2
(W11)
CN01
5
(96)
(95)
OCF1
(96)
(G)
(G)
1 2 3 4
1
5
F1
1
2
CN22
52OD1
CN23
52OD2
CN21
3
1
CN13
CN2
RB
RTS
CTS
Control Box
5
CN15
CN11
CN12
CN17
CN25
R
Output
Signal
(G)
T
3
4
52CM
220 V
COM
CN24
52CT
ON
Dip Switch
ON
Off (Default)
Dip Switch
#1 : On : Fan Stop Mode (Fan Auto)
Off : Fan Operate Mode (Fan On)
#2 : N/A
#3 : N/A
#4 : On : The Buzzer Sound Disabled
1 2 3 4
(98)
OCF1
(97)
(98)
IOLC
IOLF2
IOLF1
(G)
(W22)
AP
Attachment Plug
TB1
Terminal Block
TB2
Terminal Block
TB3
Terminal Block
TB4
Terminal Block
MF1
Evaporator Fan Motor
MF2
Condenser Fan Motor
G
IOLF1
RPHR
Reverse Phase Protector
MCF
Fan Motor Relay
MCC
Compressor Motor Relay
HPRS
High Pressure Switch
OCF1
Overcurrent Relay MF1
OCF2
Overcurrent Relay MF2
MC
Compressor Motor
RB
Relay Board
CTS
Freeze Protection Thermistor
CB
Control Board
Grounding
RTS
Room Thermistor
CN3
CN1
Connector for RPHR
CN2
Connector for RTS
Connector for HPRS
Inner Overload Relay of MF1
IOLC
IOLF2
Inner Overload Relay of MF2
Inner Overload Relay of Compressor