REMKO CMF / CMT

General
In the event of system malfunc-
tions, fi rst check the control system
cabling and components for cor-
rectness.

Sensors
All of the sensors can be checked
from the "General/ Service/Sensor
test" screen. All of the connected
sensors have to appear here with
plausible measured values.

Actuators (mixers, pumps)
All of the actuators can be checked
from the "General/ Service/relay
test" screen. This screen enables all
of the relays to be checked indi-
vidually. This enables the correct
connection of these components
to be easily checked (e.g. mixer
direction of rotation).

Communication
The bus and sensor cables should
be checked in the event of com-
munication faults. The cables are
to be spatially separated from
power lines. The polarity is also to
be checked.

Troubleshooting

A corresponding error code ap-
pears on the heat pump manager
display in the event of a fault on
the heating system. The meaning
of the displayed error codes can be

taken from the following table.
The system should be restarted
after a brief shut-down after the
fault has been rectifi ed (mains
switch). Subsequently the heat

Display

Fault description

E 54

Heat pump fault

E 69

Failure or short in supply sensor HK2

E 70

Failure or short in supply sensor HK1, Multifunction
sensor 1

E 71

Failure or short in lower buffer sensor

E 72

Failure or short in top buffer sensor

E 75

Failure or short external sensor

E 76

Failure or short domestic water sensor

E 78

Failure or short collector sensor

E 80

Failure or short room sensor heating circuit 1

E 81

EEPROM error. The invalid value has been replaced by
the default value. Check parameter values!

E 83

Failure or short room sensor heating circuit 2

E 84

Fault humidity sensor

E 90

Address 0 and 1 on bus. Bus codes 0 and 1 may not
be used simultaneously.

E 91

Bus code assigned. The set bus code is already being
used by another device.

E 135

Failure or short lower WW buffer sensor, Multifunction
sensor 2

E 136

Failure or short heating appliance sensor 2, collector
sensor 2, Multifunction sensor 3

E 137

Failure or short in collector sensor 1, Multifunction
sensor 4

E 140

Failure or short in return line sensor cooling mode

E 200 - E 207

Communication heating appliance 1 to WE 7

E 220 - E 253

Communication BM 0 to BM 15

E 240

Communication Manager

E 241

Communication (individual) heating appliances

E 242

Communication mixer

E 243

Communication Solar

Info 51 *

Information: Maintenance required

Info 55

Information: Heat pump cut off

* Customer Service appears on the
display
.

The "Info 55" display (heat
pump cut-off) appears during
each energy supply company
off-period.

NOTE

pump manager will re-start, auto-
matically reconfi gure and continue
to operate with the set values.

34