2 adjusting the configuration for denmark, 3 adjusting the configuration for france, 4 adjusting the configuration for austria – SMA SI 3.0-11 Quick Reference Guide V.3.0 User Manual

Page 47

Advertising
background image

SMA Solar Technology AG

7  Commissioning

Installation - Quick Reference Guide

Ersatzstrom-IS-en-30

47

7.3.2 Adjusting the Configuration for Denmark

When using the Sunny Island 6.0H / 8.0H in Denmark, you must reduce the discharge/charging current (default setting:

max. 20.0 A).
When using the Sunny Island 3.0M / 4.4M in Denmark, you can retain the default setting of the discharge/charging

current (default setting: max. 16.0 A).

Requirement:

☐ The extended configuration must be performed within the first ten operating hours of the Sunny Island inverter,

otherwise an SMA Grid Guard code is required in order to change grid-relevant parameters (application form for

the SMA Grid Guard code available at www.SMA-Solar.com).

☐ The country data set of the Sunny Island inverter must be set to VDE-AR-4105 (see Section 7.1 "Basic Configuration

of the Sunny Island Inverter", page 40).

Procedure:

1. Switch to expert mode on the Sunny Remote Control (see the Sunny Island inverter operating manual).
2. Set the parameter 210.03 InvChrgCurMax to 16.0 A.

7.3.3 Adjusting the Configuration for France

The following limiting values must be adjusted in order to meet the requirements of the Union technique de l’électricité

(UTE):

• Maximum power frequency
• The upper frequency difference for valid grid connection
• Minimum observation time for grid voltage and frequency before grid connection

Requirement:

☐ The extended configuration must be performed within the first ten operating hours of the Sunny Island inverter,

otherwise an SMA Grid Guard code is required in order to change grid-relevant parameters (application form for

the SMA Grid Guard code available at www.SMA-Solar.com).

☐ The country data set of the Sunny Island inverter must be set to VDE-AR-4105 (see Section 7.1 "Basic Configuration

of the Sunny Island Inverter", page 40).

Procedure:

1. Switch to expert mode on the Sunny Remote Control (see the Sunny Island inverter operating manual).
2. Set the parameter 232.07 GdFrqMax to 50.6 Hz.
3. Set the parameter 232.15 GdFrqMaxDel to 0.05 Hz.
4. Set the parameter 232.08 GdVldTm to 30 s.

7.3.4 Adjusting the Configuration for Austria

If your grid operator does not permit frequency-dependent control of active power feed-in in the case of overfrequency,

you must switch off this function (see VDE-AR-N 4105 item 5.7.3.3).
If your grid operator specifies a maximum grid feed-in per line conductor, you must reduce the discharge/charging

current (default setting in the Sunny Island is 20.0 A).

Requirement:

☐ The extended configuration must be performed within the first ten operating hours of the Sunny Island inverter,

otherwise an SMA Grid Guard code is required in order to change grid-relevant parameters (application form for

the SMA Grid Guard code available at www.SMA-Solar.com).

☐ The country data set of the Sunny Island inverter must be set to VDE-AR-4105 (see Section 7.1 "Basic Configuration

of the Sunny Island Inverter", page 40).

Advertising
This manual is related to the following products: