SMA AUTOMATIC SWITCH BOX M-20 User Manual
Page 60
Advertising
![background image](/files/818786/content/doc060.png)
10 Technical Data
SMA Solar Technology AG
60
AS-BOX-M_L-IA-IEN110320
Installation Guide
Feed in signal connection
Internal consumption
Climatic Conditions
Nominal AC voltage range
195.5 V … 264 V
Maximum cross-section of the insulated conductor to be
connected
2.5 mm²
Stripping length of the insulated conductors
10 mm … 12 mm
Internal consumption during the day
114 W
Internal consumption at night
69 W
Operating temperature range
*
*
At an ambient temperature of 35 °C, take derating into account.
− 25 °C … +50 °C
Air humidity
0 % … 100 %