When the output is connected to relay and solenoid – Yaskawa MP2000 Series Machine Controller Safety Precautions User Manual

Page 14

Advertising
background image

E-12

The power ON sequences and circuit configuration examples are as shown below.

„

When the output is connected to Relay and Solenoid

Configure the circuit so that the power supply to the output device (relay, solenoid, etc.) will
be turned ON upon the CPU RUN output (interlock output) of the MP2000 module.

<Power ON Sequence>

<Circuit Configuration Example>

MP2000 module

power supply

CPU RUN signal

Output device power supply

OFF

ON

OFF

OFF

ON

ON

DC power supply

Interlock output

CPU RUN

OB00000

SB000004

MP2000 module

RA1

Output device

RA1

DC power supply

Output device

power supply

ON relay

Power supply

MP2000 module

SB00004:Normally the ON coil turns ON with proper operation of the CPU.
0B00000:Interlock output

Advertising