Exide Technologies PORTFOLIO PAR20 User Manual

Page 21

Advertising
background image

ations in cell temperatures greater than 5°F (2.78°C) in the

series string at a given time, due to environmental condi-

tions or module arrangement, can cause low cells.
14.1

Equalizing Frequency

An equalizing charge should be given when any of the fol-

lowing conditions exist:

A. The float voltage of any cell is less than 2.18 VPC.

B. A recharge of the battery is required in a minimum time

period following an emergency discharge.

C. Individual cell(s) float is more than +/- 0.05 volts from

average.

D. Accurate periodic records (See Section 15) of individ-

ual cell voltages show an increase in spread since the

previous semi-annual readings.

An annual equalize charge is recommended to help

ensure uniform cell performance.

14.2

Equalizing Charge Method

Constant voltage charging is the method for giving an

equalizing charge. Determine the maximum voltage that

may be applied to the system equipment. This voltage,

divided by the number of cells connected in series, will

establish the maxi-mum volts per cell that may be used to

perform the equalizing charge in the shortest period of time

(not to exceed 2.35 VPC applicable at 77°F, 25°C). Refer

to Table E for voltages and recommended time periods.

NOTE: Charge volts listed in Table E are for 77°F. For other

temperatures a compensation factor of .003 V/°F (.0055 V/°C)

per cell is recommended. The minimum voltage is 2.20 VPC.

The maximum voltage is 2.35 VPC. Temperature correction

does not apply outside of this range.

V corrected = V25°C - ((T actual-25°C) x (.0055 V/°C)) or V

corrected = V77°F - ((T actual-77°F) x (.003 V/°F))

See Appendix A for standard values.

A. Set constant voltage charger to maximum setting without

exceeding 2.35 VPC.

Example: For a target charge of 2.35 VPC on a 24-cell sys-

tem, you would set the charger voltage to 56.4 volts.

B. Record time and current at regular intervals – every hour

as a minimum.

C. Continue charging the battery until there is no further drop

in charge current over 3 consecutive hours.
D. When the current has stabilized, proceed to step 2.

A. Continue the charge for the time listed in Table E depend-

ing on the charger voltage setting. The time is IN ADDITION

to the time spent charging in Step 1.

Example, charge for 12 hours if the charger voltage is set to

2.35 VPC.

TABLE E

EQUALIZE CHARGE (77°F)

CELL VOLTS

TIME (HOURS)

2.30

24

2.33

18

2.35

12

B. Record cell voltages hourly during the last 3 hours of the

charge time. If, after the charge time has completed, but the

lowest cell voltage has continued to rise, you may extend the

charge, monitoring cell voltages hourly, until the lowest cell

voltage ceases to rise.

C. Proceed to Step 3.

The Equalize charge is now complete. Charger voltage can

now be reduced to float voltage setting per Section 13.2. For

a target float charge of 2.25 VPC on a 24-cell system, you

would set the charger voltage to 54 volts.

SECTION 15: RECORDKEEPING

15.0

Pilot Cell

A pilot cell is selected in the series string to reflect the

general condition of cells in the battery. The cell selected

should be the lowest cell voltage in the series string fol-

lowing the initial charge. See Section 12.0 - Initial Charge.

Reading and recording pilot cell voltage monthly serves

as an indicator of battery condition between scheduled

overall individual cell readings.

15.1

Voltmeter Calibration

Panel and portable voltmeters used to indicate battery float

voltages should be accurate at the operating voltage value.

The same holds true for portable meters used to read individ-

ual cell voltages. These meters should be checked against a

standard every six months and calibrated when necessary.

15.2

Records

The following information must be recorded at installation,

and annually for every year of operation after installation.

These records must be maintained throughout the life of

the battery and made available for review by GNB repre-

sentatives for capacity or life related warranty claims.

Failure to collect and store these maintenance data will

void the warranty. Please review the warranty statement

specific to the application for any additional requirements.

STEP 3

STEP 2

STEP 1

21

Advertising