Larm codes – Riello UPS Sentinel Dual (High Power) (3.3 - 10 kVA) User Manual
Page 66
66
P
ROBLEM SOLVING
A
LARM CODES
By using a sophisticated self-test system, the UPS can check and report on the display panel any problems
and/or failures that could occur during normal operation of the equipment. In case of a problem, the UPS
signals the event by posting on the display the code and type of alarm present (FAULT and/or LOCK).
FAULT
The FAULT type reports may be divided into three categories.
Failures: these are “minor” problems that do not result in the UPS stopping but they limit its
performance or prevent certain features being used.
CODE
DESCRIPTION
A06
Temperature sensor1 less than 0°C
A08
Temperature sensor2 less than 0°C
A11
Input relay stuck (does not open)
A54
Load > threshold set by user
A61
Batteries need replacement
A62
Battery pack missing or not connected
A63
Waiting for batteries to recharge
Alarms: these problems are more critical than the failures because – if they continue – they could
cause the UPS to stop, even in a very short time frame.
CODE
DESCRIPTION
F03
Auxiliary power supply incorrect
F04
High temperature on heat sinks
F05
Temperature Sensor1 broken
F07
Temperature Sensor2 broken
F10
Input fuse broken or input relay stuck (does not close)
F13
Capacitor precharging failure
F21
Capacitor bank overvoltage
F40
Inverter overvoltage
F41
D-C voltage on output
F42
Inverter voltage not right
F43
Inverter undervoltage
F50
Overload: load > 103%
F51
Overload: load > 110%
F52
Overload: load > 150%
F53
Short-circuit
F55
Waiting for load reduction before return to inverter
F60
Battery overvoltage