The following table shows all the possible configurations available to adapt the UPS to the user’s
requirements.

KEY:


Indicates that the configuration can be changed from the display panel as well
as by means of the configuration software.


Indicates that the configuration can only be changed via the configuration
software.

FUNCTION

DESCRIPTION

PREDEFINED

POSSIBLE CONFIGURATIONS

MODE

Output frequency

To select the nominal

output frequency

Auto

50 Hz
60 Hz
Auto: automatic sensing from the input

frequency

Output voltage

To select the nominal

output voltage

230V

220V
230V
240V
220 ÷ 240 in 1V steps

(only via software)

Operating mode

To select one of the 4

different operating

modes

ON LINE

ON LINE
ECO
SMART ACTIVE
STAND-BY OFF

Start-up delay

Delay before

automatic restart after

the mains returns

5 sec.

Disabled
1 ÷ 255 in 1 sec. steps

Shutdown due to

minimum load

Automatic shutdown

of the UPS in

operation from the

battery if the load is

less than 5%

Disabled

Enabled
Disabled

Back up time

limit

Maximum time of

operation from the

battery

Disabled

Disabled (full battery discharge)
1 ÷ 65000 in 1 sec. steps

End of discharge

alert

Estimated remaining

back up time for the

end of discharge alert

3 min.

1 ÷ 255 in 1 min. steps

Battery test

Time interval for the

automatic battery test

40 hours

Disabled
1 ÷ 1000 in 1 hour steps

=

=