Emerson OpenComms-485 User Manual

Page 8

Advertising
background image

REV. 5

7/6/2007

Liebert Monitoring Group –Development

5

UPS Power Not Redundant

10296

1

1

Power Module Failure

10298

1

1

Battery Module Failure

10299

1

1

Power Module Warning

10300

1

1

Battery Module Warning

10301

1

1

Data Point

Input

Register

Holding

Register

# of

Reg. Scale Notes/ Units

Number Of Input Lines

30004

40004

1

1

Bits 12 - 15

Number Of Bypass Lines

30004

40004

1

1

Bits 4 - 7

Number Of Output Lines

30004

40004

1

1

Bits 8 - 11

Number Of Power Mod.

30010

40010

1

1

Number Of Battery Modules
Installed

30011

40011 1

1

Device Maximum Frame
Capacity

30023

40023

2

1

Device System Capacity

30025

40025

2

1

VA

Nominal Input Voltage

30027

40027

1

1

V

Nominal Output Voltage

30028

40028

1

1

V

Nominal Static Bypass
Switch Voltage

30029

40029

1

1

V

Nominal Input Frequency

30031

40031

1

10

Hz

Nominal Output Frequency

30032

40032

1

10

Hz

Nominal Power Factor

30033

40033

1

100

Nominal Battery Voltage

30034

40034

1

1

V

Auto Restart Delay

30051

40051

1

1

seconds

Device Auto Restart
Percent Setpt

30052

40052 1

1

%

Device Low Battery Time

30053

40053

1

1

min

Next Battery Auto Test
Time

30057

40057 1

1

minutes

Overload Alarm Limit

30067

40067

2

1

VA

Minimum Redundant Power
Modules

30074

40074

1

1

Load (Apparent Power)

30102

2

1

VA

Load (Real Power)

30104

2

1

W

Load / Capacity

30106

1

1

%

Input Frequency

30107

1

10

Hz

Output Frequency

30108

1

10

Hz

Bypass Frequency

30109

1

10

Hz

Battery Charge Status

30112

1

1 - 100% Charged
2 - Less than 100% Charged
3 - Charging
4 - Discharging
5 - Float Charging
6 - Equalize Charging

Battery Voltage

30113

1

1

V

Battery Time Remaining

30115

1

1

min