MVI56-LTQ ♦ ControlLogix Platform

Configuring the MVI56-LTQ Module

Limitorque Valve Actuator Master Communication Module

User Manual

ProSoft Technology, Inc.

Page 23 of 98

August 30, 2010

2.3

Configuration Data

This section contains listings of the MVI56-LTQ module’s configuration that is
read from the ControlLogix processor when the module first initializes.

2.3.1 BaudRate

The baud rate at which the port is to operate. The available configurations are as
follows:

Value

Baud Rate

1200

1200 Baud

2400

2400 Baud

4800

4800 Baud

9600

9600 Baud *

19200

19200 Baud

38400

38400 Baud

57600

57600 Baud

115200

115200 Baud

* Limitorque Field Unit Factory Default Setting

2.3.2 MsgRespTm

This register represents the message response timeout period in 1 millisecond
increments. This is the time which a port configured as a Master will wait before
re-transmitting a command if no response is received from the addressed slave.
The value is set depending on the expected slave response times.

A value of 200 milliseconds should be the minimal setting. Values from 200 to
65535 (0xffff) are permitted.

2.3.3 MaxSlaves

This value is used by the module to optimize the number of slaves polled by the
module. The value entered here can range from 1 to 150, and should always
meet or exceed the last slave in the Active Slave Table.

2.3.4 BTRMax

This value is not used in the current version of the software.