7.1.9 Minimum Response Delay

0

TO

65535

This parameter is used only when the port is configured as a slave. It sets the
number of milliseconds to wait before responding to a command received on the
port from a remote Master. This delay is sometimes required to accommodate
slower Master devices.

7.1.10 Use CTS Line

Y

ES

or N

O

This parameter specifies if the Clear To Send (CTS) modem control line is to be
used or not. If the parameter is set to N

O

, the CTS line will not be monitored. If

the parameter is set to Y

ES

, the CTS line will be monitored and must be high

before the gateway will send data. Normally, this parameter is required when
half-duplex modems are used for communication (2-wire). This procedure is
commonly referred to as hardware handshaking.

7.1.11 Response Timeout

0

TO

65535 milliseconds

This parameter sets the command response timeout period in 1 millisecond
increments. This is the time that a port configured as a Master will wait for a
response from the addressed slave before re-transmitting the command (Retries)
or skipping to the next command in the Command List. The value to set depends
on the communication network used and the expected response time (plus a little
extra) of the slowest device on the network.

7.1.12 Retry Count

0 to 10

This parameter specifies the number of times a command will be retried if it fails.