ProSoft Technology 5301-MBP-ASCII User Manual
Page 23
MBP ♦ ProLinx Gateway
MBP Protocol Configuration
Modbus Plus
Protocol Manual
ProSoft Technology, Inc.
Page 23 of 52
May 12, 2011
3.1.3 Global Input Update Timeout
0 to 65535
This value defines the timeout period (0 to 65535 milliseconds) for receiving
Global Input Data from other nodes on the network. After the timeout period has
been exceeded, the Timeout Error will be returned in the Global In Update Status
data set. A value of 0 will result in the default value of 1000 milliseconds (1
second).
3.1.4 Master Command Timeout Preset
0 to 65535
This parameter defines the number of milliseconds (0 to 65535) to wait for a
response to a master command issued by the module on the network. If a
timeout condition exists for a command, it will be reflected in the Master
Command List Status data area. A value of 0 will result in a value of 1000 (1
second) for the parameter.