C7772A, F, G WALLPLATE TEMPERATURE SENSOR

3

68-0213—04

Table 1. C7772 Models.

NOTE: TCR = temperature coefficient of resistance.

Mounting

To mount on conduit box (see Fig. 2):

1. Remove the appropriate knockout on the standard utility

conduit box for the application.

2. Make wiring connections to the system components.

IMPORTANT

Level only for appearance. The sensor functions

normally even when not level.

3. Use the No. 6 screws provided to mount the wallplate to

the conduit box.

Wiring

CAUTION

Electrical Shock or Equipment Damage Hazard.

Can shock individuals or short equipment

circuitry.

Disconnect all power supplies before installation.

CAUTION

Erratic System Operation Hazard.

Failure to follow proper wiring practices can introduce

disruptive electrical interference (noise).

Keep wiring at least one foot away from large inductive

loads such as motors, line starters, lighting ballasts,

and large power distribution panels.

Shielded cable is required in installations where these

guidelines cannot be met.

Ground shield only to grounded controller case.

IMPORTANT

• Temperature sensor wiring can be sized from

16 to 20 AWG depending on the application.

• The maximum length of wire from a device to the

wallplate sensor is 300 ft (91m).

NOTE: Erratic temperature readings from a sensor can be

caused by the wiring practices described below.

These must be avoided to assure proper operation:

1.

Do not route temperature sensor wiring with

building power wiring, next to control contactors,

near light dimming circuits, electric motors or

welding equipment.

2.

Avoid poor wiring connections.

3.

Do not mount sensor in an incorrect environment.

Connect the low voltage wiring from the controller terminals to

the sensor screw terminals and tighten. See Fig. 2.

Fig. 2. Mounting, wiring for C7772.

OPERATION

The C7772 Wallplate Temperature Sensor provides a resistive

output signal proportional to the sensed room temperature.

Model

Sensor Type

Nominal Resistance

Resistance-Temperature

Curve Type

Lead Wire

Color

C7772A

20K NTC Thermistor

20,000 ohms at 77°F (25°C)

Non-linear Negative TCR

Green/Blue

C7772F

10K Ohm NTC Type II Thermistor

10,000 ohms @ 77°F (25°C)

Non-linear Negative TCR

Green/White

C7772G

10K Ohm NTC Type III Thermistor

10,000 ohms @ 77°F (25°C)

Non-linear Negative TCR

White/White

STANDARD UTILITY

CONDUIT BOX

CONNECTOR

LOCKNUT

AND

CONDUIT

TO APPROPRIATE

SYSTEM

COMPONENTS

BLANK

FACEPLATE

M16296