Troubleshooting, Current conversion formula, Troubleshooting current conversion formula – Honeywell CTP-20 User Manual

Page 4

Advertising
background image

SOLID CORE AND SPLIT CORE 4-20 MA OUTPUT CURRENT SENSORS

Automation and Control Solutions
Honeywell International Inc.

Honeywell Limited-Honeywell Limitée

1985 Douglas Drive North

35 Dynamic Drive

Golden Valley, MN 55422

Toronto, Ontario M1V 4Z9

customer.honeywell.com

® U.S. Registered Trademark
© 2007 Honeywell International Inc.
62-0245—01 C.H. Rev. 06-07

TROUBLESHOOTING

CURRENT CONVERSION FORMULA

To convert the current sensor output signal to a current
reading.

Current reading = mA output/20 mA x Amp Span.
For example:
For a reading of 4 mA with a 0-250 Amp span:
Current reading = (4 mA/20 mA) x 250 A = 0 Amp.
(0/16) X 250 = 0

NOTE: 4 mA = 0 Amps

20 mA = 250 Amps

Problem

Solution

No reading

Confirm that you have +12 to 30 Vdc in series with the current sensor output terminals

and the analog input of the control panel.

Check the polarity of the circuit.
Verify that the terminals are screwed down, wires are firmly in place.
Disconnect the input to the control panel and then insert a current meter (mA range) in

series with the current sensor output to verify that the circuit is working properly.

Erratic readings

Verify that the wires are terminated properly.
Check that the +12 to 30 Vdc input is clean. In areas of high RF interference, shielded

cable may be necessary to stabilize signal.

Inaccurate readings

If you suspect that the current sensor is not reading within the accuracy specifications,

please contact the factory for assistance.

Advertising
This manual is related to the following products: