Grounding, Electrical specifications, Ac power cables – HP RP3440 User Manual

Page 42: Circuit breaker, Grounding electrical specifications, Ac power cables circuit breaker, Power cables

Advertising
background image

Table 2-2 Server Dimensions and Values (continued)

Values

Dimension

0.2 m

2

(2.1 sq. ft.)

Pedestal footprint

2U

Rack units

Grounding

The site building shall provide a safety ground or protective earth for each AC service entrance
to all cabinets.

Install a PE (protective earthing) conductor that is identical in size, insulation material, and
thickness to the branch-circuit supply conductors. The PE conductor must be green with yellow
stripes. The earthing conductor is to be connected from the unit to the building installation earth
or, if supplied by a separately derived system, at the supply transformer or motor-generator set
grounding point.

Electrical Specifications

This section provides electrical specifications for the server.

AC Power Cables

Table 2-3

lists the power cables available for use with the HP 9000 rp3410 and rp3440 servers.

Table 2-3 Power Cables

Country

Description

Part Number

South Africa

Power Cord C15/S Africa 2.5m black CA ASSY 917

8120-5341

United Kingdom
Hong Kong

Singapore

Power Cord C13/BS-1363 2.3m black CA ASSY 900

8120-1351

Australia

Power Cord C13/AS-3112 2.0m gray CA ASSY 901

8120-1369

Europe

Power Cord C13/CEE 7 2.0m black CA ASSY 902

8120-1689

Switzerland

Power Cord C13/SEV 12 2.0m black CA ASSY 906

8120-2104

Denmark

Power Cord OPT-912 3-COND 2.25-M-LG 912

8120-6814

North America (250#V)
Japan

Power Cord C13/6-15P 0.0m black CA ASSY 904 / 918

8120-0698

Israel

Power Cord OPT-919 3-COND 2.3-M-LG 919

8120-6800

Argentina

Power Cord C15/CEI 23-16 2.5m black CA ASSY 920

8120-8390

Chile

Power Cord C15/CEI 23-16 2.5m black CA ASSY 921

8120-8389

China

Power Cord C13/GB-1002 2.236m gray CA ASSY 922

8120-8376

South America

Power Cord OPT-927 3-COND 2.3-M-LG FLNT 927

8121-0668

All

C13/C14 Jumper cord

8120-6514

Circuit Breaker

The marked electrical for the server is 7.2 amps. The recommended circuit breaker size is 12 amps
per line cord (two maximum) for North America. For countries outside North America, consult
the local electrical authority that has jurisdiction for the recommended circuit breaker size.

42

System Specifications