L8124A,C,E,L AND M AQUASTAT® RELAYS

Automation and Control SolutionsAutomation and Control Solutions

Honeywell

Honeywell Limited-Honeywell Limitée

1985 Douglas Drive North

35 Dynamic Drive

Golden Valley, MN 55422

Scarborough, Ontario
M1V 4Z9

On the L8124M, the burner and circulator circuits are
separately controlled; the low limit controls the burner
circuit (R-B) as described above, while the low voltage
thermostat directly controls the circulator circuit.
See Fig. 13.

Fig. 13. L8124M single zone connections

and internal schematic.

SETTING

Follow the boiler manufacturer recommendations when
making the L8124 settings. The high limit setting must be
at least 20°F (11°C) higher than the low limit setting. Set
the indicators over the selected temperature marks. The
low limit differential is set by turning the differential
adjustment knob to the desired amount of differential.
The thermostat heat anticipator should be set at 2.0A.

CHECKOUT

Put the system into operation and observe each function
through at least one complete cycle. Be sure the control
operates as intended.

M8804

L1
(HOT)

L2

1

3

1

2

3

2

POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.

CONTROL CASE MUST BE CONNECTED TO EARTH
GROUND. USE GROUNDING SCREW PROVIDED.

B1 IS 1/4 IN. TAB TERMINAL.

LINE VOLTAGE

OIL BURNER

RELAY OR

GAS VALVE

LINE VOLTAGE
CIRCULATOR

C2

C1

B2

B1

R

B

HIGH
LIMIT

ZC

1K1

B

R

W

LOW LIMIT

1K

L2

L1

G

T

T

L8124M

LOW VOLTAGE
THERMOSTAT