Configuring the accessory loops, 1 fields – Honeywell Stryker VAV 62-2030-01 User Manual
Page 17

STRYKER VAV USER GUIDE
17
62-2030—01
RELATED TOPICS
“1. About Stryker VAV” on page 2
10. CONFIGURING THE ACCESSORY LOOPS
Use this page to configure accessory loops for Stryker VAV device on the LON network.
To configure Accessory Loops:
10.1 Fields
Heating Integral Time
Value must be configured based on reheat configuration.
Heating Derivative
Time
Value must be between 0 to 9000 sec.
Table 10. PID Names. (Continued)
Name
Definition
Reheat Type
Integral Time (sec)
modulating
2400
1 stage
3100
2 stage
2500
3 stage
1650
4 stage
1200
Step
Action
1
From the left pane of the
VAV Configuration Wizard, select Accessory Loops.
The
Loop1 page appears.
2
Enter information in the available fields.
3
From the menu bar, click
Loop2. The Loop2 page appears.
4
Enter information in the available fields.
5
Click
Next to display the Custom wiring page.
6
Click
Undo All to revert to the last saved settings.
7
Click
Finish to save settings to station.
Table 11. Accessory Loop Fields.
Name
Definition
Loop Name
Enter a custom name for the loop.
NOTE: A maximum length of 18 characters is allowed. The following characters are valid
a-z, A-Z, 0-9, under-score and space.
Outputs
Accessory loop can be configured to drive a modulating output, upto 3 staged outputs and an
auxiliary digital output. The outputs can be configured only when the required pins are available/
"3. Configuring the Outputs" section to configure output parameters.
Staged Control action: Staged outputs can be configured with either as conventional staged
outputs or as staged outputs with thermostat using 3 Cycles per Hour.
Inputs
Please refer the
"4. Configuring the Inputs" section.
To use shared inputs:
Select the
Shared Input from the Input Name drop down list.
To use main application output as an input:
Select the
Main Application from the Input name drop down list.