Gcvm96 a, Irflow, Eating – Goodman Mfg VARIABLE-SPEED GAS FURNACE GMVM96 User Manual

Page 9: Peeds

Advertising
background image

8

www.goodmanmfg.com

SS-GMVM96

SS-GMVM96

www.goodmanmfg.com

9

P

roduct

S

PecificationS

P

roduct

S

PecificationS

GCVM96 a

irflow

d

ata

— H

eatiNG

s

peeds

GCVM960604CX
ACVM960604CX

(Rise Range: 20 - 50°F)

GCVM960805DX
ACVM960805DX

(Rise Range: 20 - 50°F)

Adjust

Tap

CFM *

Rise (°F)

Adjust

Tap

CFM *

Rise (°F)

Minus(-)

1,098

48

Minus(-)

1,440

49

Normal

1,220

44

Normal

1,600

44

Plus (+)

1,342

40

Plus (+)

1,760

40

Minus(-)

1,206

44

Minus(-)

1,539

46

Normal

1,340

40

Normal

1,710

41

Plus (+)

1,474

36

Plus (+)

1,881

38

Minus(-)

1,314

40

Minus(-)

1,620

44

Normal

1,460

36

Normal

1,800

39

Plus (+)

1,606

33

Plus (+)

1,980

36

Minus(-)

1,431

37

Minus(-)

1,719

41

Normal

1,590

33

Normal

1,910

37

Plus (+)

1,749

30

Plus (+)

2,101

34

* @ .1" - .5" w.c. ESP

* @ .1" - .5" w.c. ESP

GCVM961005DX

(Rise Range: 25 - 55°F)

Adjust

Tap

CFM *

Rise (°F)

Minus(-)

1,557

56

Normal

1,730

51

Plus (+)

1,903

46

Minus(-)

1,593

55

Normal

1,770

49

Plus (+)

1,947

45

Minus(-)

1,656

53

Normal

1,840

48

Plus (+)

2,024

43

Minus(-)

1,683

52

Normal

1,870

47

Plus (+)

2,057

43

* @ .1" - .5" w.c. ESP

Notes

• All furnaces ship as high speed for cooling. Installer must adjust blower speed as needed.
• For most jobs, about 400 CFM per ton when cooling is desirable.
• Operation is recommended below .5” w.c. ESP in heating mode. Operating CFM between .5” and .8” w.c. is tabulated for

cooling purposes only.

• High-fire CFM shown. CFM will vary proportionally with the gas valve BTU/H input.