Specifications – Murphy BCEG-24-20 User Manual

Page 18

Advertising
background image

Section 75

00-02-0615

02-29-08 -

14 -

Specifications

Power Supply

• Nominal

operating

voltages – 120V Units

• Permissible voltage variation - ± 6% of nominal
• Nominal operating frequency – 50/60Hz

DC Charge Output

• Maximum current ADC – 20
• Nominal voltage VDC – 12 or 24
• Float/boost

voltages

These are factory preset for specified batteries, typical settings are as follows:

Vented lead acid – Float voltage – 12V / 13.6V and 24V / 27.2V
Vented lead acid – Boost voltage – 12V / 14.1V and 24V / 28.2V

Charge Fail Output

• Relay type – volt free SPDT contacts relay de-energized on fault.
• Contact rating – 1A @ 30VDC (resistive load)

General

• Transformer – Single phase 50-60 Hz Class 155 (F)
• Operating temperature - +14°F to +131°F (-10°C to +55°C)
• Wall mounted enclosure models
• BCEG-12-10, BCEG-24-10 – dimensions 10.9”/278mm(W) x 4.7”/120mm(L) x

11”/280mm(H); weight 22 pounds / 10.0Kg

• BCEG-24-20 – dimensions 11.8”/300mm(W) x 11.8”/300mm(L) x 8.3”/210mm(H), weight

38.5 pounds / 17.5Kg

• EMC emission/immunity – EN58801-2 / EN50082-2