Johnson Controls TCGD30 User Manual

Page 2

Advertising
background image

415571-UTG-C-0309

2

Johnson Controls Unitary Products

All dimensions are in inches. They are subject to change with-
out notice. Certified dimensions will be provided upon request.

Physical and Electrical Data

MODEL

TCGD30

S43S1

TCGD36

S43S1

TCGD42

S43S1

TCGD48

S43S1

TCGD60

S43S1

TCGD30

S44S1

TCGD36

S44S1

TCGD42

S44S1

TCGD48

S44S1

TCGD60

S44S1

Unit Supply Voltage

208-230V, 3

 60Hz

460V, 3

 60Hz

Normal Voltage Range

1

187 to 252

432 to 532

Minimum

Circuit

Ampacity

11.4 12.3 16.3 15.5 23.9 9.4 7.1 8.0 7.9 13.5

Max. Overcurrent Device Amps

2

15 20 25 25 40 15 15 15 15 20

Min. Overcurrent Device Amps

3

15 15 20 20 25 15 15 15 15 15

Compressor Type

Recip

Recip Recip Recip Scroll Recip Recip Recip Recip Scroll

Compressor Amps

Rated

Load

8.1 8.6 11.8

11.2

17.9 6.6 4.5 5.2 5.1 9.6

Locked

Rotor

63 68 88 88 120 30 34 44 44 70

Crankcase

Heater

No No No No No No No No No No

Fan

Motor

Amps

Rated

Load

1.2 1.5 1.5 1.5 1.5 1.2 1.5 1.5 1.5 1.5

Fan

Diameter

Inches

17.5 22 22 22 22 17.5 22 22 22 22

Fan Motor

Rated

HP

1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4 1/4

Nominal

RPM

1100 850 850 850 850 1100 850 850 850 850

Nominal

CFM

2050 3200 2950 2950 3600 2050 3200 2950 2950 3600

Coil

Face

Area

Sq.

Ft.

9.6 13.07 14.16 14.16 18.68 9.6 13.07 14.16 14.16 18.68

Rows

Deep

1 1 1 1 1 1 1 1 1 1

Fin

/

Inches

23 23 23 23 23 23 23 23 23 23

Liquid

Line

Set

OD

(Field

Installed)

3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8

Vapor

Line

Set

OD

(Field

Installed)

3/4 3/4 7/8 7/8 7/8 3/4 3/4 7/8 7/8 7/8

Unit Charge (Lbs. - Oz.)

4

3 - 14

4 - 9

4 - 5

4 - 9

5 - 6

3 - 14

4 - 9

4 - 5

4 - 9

5 - 6

Charge

Per

Foot,

Oz.

0.62 0.62 0.67 0.67 0.67 0.62 0.62 0.67 0.67 0.67

Operating

Weight

Lbs.

131 145 173 173 195 131 145 173 173 195

1. Rated in accordance with ARI Standard 110, utilization range “A”.

2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.

3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.

4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or

subtract the amount of refrigerant, using the difference in length multiplied by the per foot value. If line exceeds 25 feet, you may refer to publications
software 036-68001-001 for proper line sizing.

B

A

C

Unit

Model

Dimensions

(Inches)

Refrigerant Connection

Service Valve Size

A

1

1. Including Fan Guard.

B

C

Liquid

Vapor

30

28

23-1/2

23-1/2

3/8”

3/4”

36

28

29

29

42

30

29

29

7/8”

48

30

29

29

60

32

33-5/8

33-5/8