Johnson Controls TCGD30 User Manual

Page 4

Advertising
background image

415571-UTG-C-0309

4

Johnson Controls Unitary Products

— = Not applicable.

COOLING CAPACITY - With Air Handler Coils

UNIT

MODEL

AIR HANDLER

COIL

MODEL

1

COOLING

MODEL

W

RATED

CFM

NET MBH

SEER

EER

TOTAL

SENS.

13 SEER AC WITH MA

TCGD30S4(3,4)S1

MA12B 17

FC/MC35B

1000

29.0

21.0

13.00

11.00

MA12B 17

FC/MC43B

1000

29.0

21.0

13.00

11.00

TCGD36S4(3,4)S1

MA12B 17

FC/MC43B

1200

35.0

24.8

13.00

11.00

MA14D 24

FC/MC48D

1200

35.0

24.8

13.00

11.00

TCGD42S4(3,4)S1

MA16C 21

FC/MC43C

1400

42.0

29.2

13.00

11.00

MA14D 24

FC/MC48D

1400

42.0

29.2

13.00

11.00

MA16C 21

FC/MC48C

1400

42.0

29.2

13.00

11.00

TCGD48S4(3,4)S1

MA16C 21

FC/MC48C

1600

48.0

34.4

13.00

11.00

MA20D 24

FC/MC48D

1600

48.0

34.4

13.00

11.00

MA16C 21 FC60C 1600

48.0

34.4

13.00

11.00

MA20D 24

FC/MC60D

1600

48.0

34.4

13.00

11.00

TCGD60S4(3,4)S1

MA20D 24

FC/MC60D

1800

57.0

38.5

13.00

11.00

MA20D 24

FC/MC62D

1800

57.0

38.5

13.00

11.00

13 SEER AC WITH AHP / SHP / AHX / F*FP

TCGD30S4(3,4)S1

AHP30 17

1015

29.0

21.0

13.00

11.00

AHP36 21

1040

29.0

21.0

13.00

11.00

AHX30

17

-

1025

29.4

22.2

14.00

11.75

AHX36

21

-

1005

30.0

22.3

14.50

12.00

F4FP040 18

1050

29.0

21.0

13.00

11.00

F6FP030

17

-

1035

29.2

21.6

13.50

11.40

F6FP036

21

-

980

29.4

21.4

14.00

12.00

TCGD36S4(3,4)S1

AHP36 21

1235

35.0

24.8

13.00

11.00

AHP42 21

1255

35.0

24.8

13.00

11.00

AHX36

21

-

1225

35.2

25.0

13.50

11.50

AHX42

21

-

1190

35.4

25.2

14.00

11.80

F5FP048 24

1235

35.0

24.8

13.00

11.00

F6FP042

21

-

1290

35.8

25.8

13.50

11.50

TCGD42S4(3,4)S1

AHP42 21

1485

41.0

29.2

13.00

11.00

AHX42

21

-

1395

42.0

29.9

14.50

12.00

F5FP048 24

1455

41.0

29.2

13.00

11.00

F6FP042

21

-

1455

42.0

30.1

14.00

11.75

F6FP048

24

-

1380

41.5

29.4

13.50

11.70

TCGD48S4(3,4)S1

AHP/SHP48 24

1675 48.0 34.4 13.00

11.00

AHP/SHP60 24

1600 48.0 35.0 13.50

11.00

AHX48

24

-

1660

48.0

35.4

13.50

11.50

F5FP048 24

1600

48.0

34.4

13.00

11.00

F5FP060 24

1600

48.0

34.4

13.00

11.00

F6FP048

24

-

1625

47.0

34.8

13.00

11.30

TCGD60S4(3,4)S1

AHP/SHP60 24

1850 57.0 38.5 13.00

11.00

AHX60

24

-

1905

58.5

40.0

13.50

11.50

F5FP060 24

1900

57.0

38.5

13.00

11.00

F6FP060

24

-

1710

57.5

39.0

13.50

11.50

Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210.
Cooling MBH based on 8

°F entering air temperature, 50% RH, and rated air flow.

EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power
input in watt-hours during the same period.

1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.

Advertising