11 timing requirements, Timing requirements, Figure 3: output voltage timing – SSI America ERP2U User Manual

Page 25: Table 25: output voltage timing

Advertising
background image

SSI

ERP2U Power Supply Design Guide, V2.31

- 25 -

may be removed, then replaced with a good power supply, however, hot swap needs to work with operational as
well as failed power supplies. The newly inserted power supply may get turned on by inserting the supply into the
system or by system management recognizing an inserted supply and explicitly turning it on.

6.11 Timing Requirements

STATUS

Required

These are the timing requirements for the power assembly operation. The output voltages must rise from 10% to
within regulation limits (T

vout_rise

) within 5 to 200ms. The +3.3 V, +5 V and +12 V output voltages should start to

rise at about the same time. All outputs must rise monotonically. The +5 V output needs to be greater than the
+3.3 V output during any point of the voltage rise. The +5V output must never be greater than the +3.3V output
by more than 2.25 V. Each output voltage shall reach regulation within 50 ms (T

vout_on

) of each other during turn

on of the power supply. Each output voltage shall fall out of regulation within 400 ms (T

vout_off

) of each other

during turn off. Figure 3 and Figure 4 show the turn ON and turn OFF timing requirements. In Figure 4, the
timing is shown with both AC and PSON# controlling the ON/OFF of the power supply.

Table 24: Output Voltage Timing

Item Description

MIN MAX

Units

T

vout_rise

Output voltage rise time from each main output.

5

200

ms

T

vout_on

All main outputs must be within regulation of each
other within this time.

50

ms

T

vout_off

All main outputs must leave regulation within this
time.

400

ms

Vout

10% Vout

T

vout_rise

T

vout_on

T

vout_off

V1

V2

V3

V4

Figure 3: Output Voltage Timing

Advertising