Configuration – Liebert RCM8DO User Manual

Page 23

Advertising
background image

Chapter 3: Main Menu and SubMenus

To access the RCM8 Main Menu VIA MODEM:

1. Make sure RCM8 and attached modem are turned on and

properly configured.

2. On the remote PC, set up terminal emulation session for

dial-out access – Connect Using an attached modem, rather
than direct connect to a com port.

3. Once a connection has been established with the RCM8,

press Space Bar to initiate the log-in process.

4. Type the RCM8 password, then press Enter to gain access to

the RCM8. The factory-default password for modem access
is also “RCM8”.

5. From here, continue to Step 3 of the local login process.

Configuration

The Configuration option from the Main Menu lets you view the
current RCM8 settings.

1. Press 1 to display the Configuration menu:

RCM8 V4.0 CONFIGURATION - MON 07-05-99 18:03:20

SITE ID = WEST WING COMPUTER ROOM PAGER ID - 5551149

IN DELAY NO DIAL ALT DIAL MESSAGE

MM:SS NC A CODE B

-------------------------------------------

01 00:00 NO 1 0 0 WATER UNDER FLOOR

02 00:00 NO 1 0 0 HIGH TEMP

03 05:00 NC 2 & 1 DOOR HELD OPEN

04 00:00 NO 0 0 0 CLOGGED FILTER

05 00:00 NO 0 0 0 HIGH HUMIDITY

06 00:00 NO 0 0 0 CONTACT #6

07 00:00 NO 0 0 0 CONTACT #7

08 00:00 NO 0 0 0 CONTACT #8

RCM8 Phone Number =

Phone Number 1 = 9,5551212,,,,,911##

Phone Number 2 = A9,18007596366

Dial Prefix = ATE1X4DT

Redial Tries = 2

Redial Interval = 30

Modem = CONNECTED

Modem Baud Rate = 1200

EIA-485 Online Units =

This is a view-only screen. Use the remaining Main Menu
options to make changes or reset the values shown in this
screen.

2. Press Esc to return to the Main Menu.

Liebert RCM8

17