3 voltage programming button, 4 load level indicators—4 green, 1 amber, Figure 11 load level indicators—4 green, 1 amber – Liebert PSITM User Manual

Page 19: 5 battery level indicators—5 green, Figure 12 battery level indicators—5 green, 6 ac input indicator—green, 7 buck/boost indicator—green, 8 battery indicator—green/amber, Voltage programming button, Load level indicators—4 green, 1 amber

Advertising
background image

Controls and Indicators

15

6.3

Voltage Programming Button

The PowerSure PSI contains a Voltage Programming button that allows the operator to select

the nominal mains voltage. This setting changes the mains transfer points (low and high) of

the UPS and the nominal output voltage when operating in Battery mode. The operator can

select between 220, 230 and 240VAC output. The factory-default setting is 230VAC.
The Voltage Programming button is a push button type and is behind the plastic bezel on

the front panel of the UPS. To access the button, the front bezel must be removed.

6.4

Load Level Indicators—4 green, 1 amber

The Load Level Indicators display the approximate electrical load placed upon the UPS.
The UPS Load Level Indicators are displayed in 25% increments as shown in Figure 11.

Figure 11 Load level indicators—4 green, 1 amber

Upon detection of an output overload condition, the amber overload (>100%) indicator flashes and an

audible alarm activates. If the UPS shuts down due to an overload condition, the amber overload

(>100%) indicator illuminates (see 11.0 - Troubleshooting for details).

6.5

Battery Level Indicators—5 green

The Battery Level Indicators display the approximate battery capacity.
The approximate battery capacity is displayed when the UPS is operating in Normal, Buck/Boost, or

Battery mode.
The Battery Level Indicators are displayed in 20% increments as shown in Figure 12:

Figure 12 Battery level indicators—5 green

The PowerSure PSI is equipped with automatic and remote battery test features. The automatic test

occurs every 14 days if mains has not been interrupted; this option may be configured by the user.

Should the battery fail this test, the amber Battery Indicator will be illuminated and an alarm will

sound (see 11.0 - Troubleshooting for details).
The remote test feature functions with MultiLink 3.x software and can remotely initiate the battery

test.

6.6

AC Input Indicator—Green

The AC Input Indicator illuminates when mains power is available and within the input specifica-

tions.

6.7

Buck/Boost Indicator—Green

The Buck/Boost Indicator illuminates when the UPS is operating in Boost mode to compensate for a

low mains voltage condition. This indicator flashes when the UPS is operating in Buck mode to com-

pensate for a high mains voltage condition (see 11.0 - Troubleshooting for details).

6.8

Battery Indicator—Green/Amber

The Battery Indicator illuminates green when the UPS is operating on battery and flashes green

when a low battery condition occurs. The Battery Indicator illuminates amber when a bad battery is

detected, indicating that the batteries need to be replaced (see 11.0 - Troubleshooting for details).