Table 5 battery run times, Table 5, Battery run times – Liebert PSITM User Manual

Page 32: Table 5 - battery run times

Advertising
background image

Specifications

28

Table 5

Battery run times

Load%

1000VA

1440VA

2200VA

3000VA

Internal

Battery

(minutes)

5%

174

138

171

177

10%

118

79

73

91

20%

65

45

47

47

30%

41

28

26

28

40%

37

24

23

22

50%

26

16

16

16

60%

24

14

13

14

70%

18

10

10

10

80%

16

9

8

9

90%

12

6

6

7

100%

11

5

5

6

Internal

Battery + 1

External

Battery

Cabinet

(minutes)

5%

513

409

542 542

10%

305

265

266 257

20%

248

188

185 148

30%

177

125

135 141

40%

139

104

122 99

50%

119

72

99 67

60%

98

59

75 53

70%

75

45

55 45

80%

63

40

49 39

90%

53

35

44 34

100%

46

30

40 29

Internal

Battery + 2

External

Battery

Cabinet

(minutes)

5%

1001

828

10%

565

461

493 444

20%

409

283

291 249

30%

283

219

222 168

40%

248

177

194 148

50%

209

133

150 129

60%

166

122

137 114

70%

136

98

122 92

80%

127

84

107 71

90%

110

64

92 56

100%

98

56

77 52

Internal

Battery + 3

External

Battery

Cabinet

(minutes)

5%

1174

1001

10%

1001

655

590

20%

565

409

493 300

30%

409

283

283 240

40%

305

257

266 213

50%

274

209

222 168

60%

248

166

185 144

70%

209

136

156 129

80%

188

125

141 116

90%

145

110

131 101

100%

136

95

120 88

Internal

Battery + 4

External

Battery

Cabinet

(minutes)

5%

1174

10%

1174

828

20%

828

565

590 444

30%

513

357

395 283

40%

461

292

300 266

50%

305

257

274 222

60%

283

230

240 179

70%

257

188

203 150

80%

239

156

173 139

90%

209

136

156 129

100%

188

125

144 118

NOTE
Approximate discharge times are in minutes and at 25°C (77°F) with resistive load.

Advertising