Mounting the Liebert XDV

18

5.3.2 Hanging Stacked Liebert XDVs from the Overhead Structure

Because the upper Liebert XDV in a stacked arrangement must be positioned farther forward than

the lower Liebert XDV, the place where the hangers attach to the overhead structure must be offset

accordingly. The second row of attachment locations must be 9-7/8 inches (251mm) forward of the first

row of hanger mounting locations. This arrangement positions the stacked Liebert XDVs so that they

meet the air-intake criteria shown in Figure 10 and Figure 17.
After determining the proper for attachment to the overhead structure, hang the Liebert XDVs as

outlined in 5.2.2 - Suspending the Liebert XDV from Overhead Structures.

Figure 20 Stacked Liebert XDVs ready for suspension from overhead structure

3/8"-16 All-thread bolts,
field-supplied (four
required per Liebert XDV)

Advertising