Figure 23 hard-piped connection diagram – Liebert Cooling System XDV User Manual

Page 27

Advertising
background image

Piping

21

Figure 23 Hard-piped connection diagram

Copper Tubing
Total length of each
line from Liebert XDV
to Main; not to exceed
72" (1829mm)

Top of Liebert XDV

Return Main
(seen from end )
2-1/8" O.D.
or 2-5/8" O.D.

Recommended Arc

Acceptable Arc

5/8” Refrigerant -Grade
Full-Port Ball Valve
Field-Supplied and
Field-Installed

Supply Main
(seen from end )
1-1/8" O.D.
or 1-3/8" O.D.

1/2” Refrigerant-Grade
Full-Port Ball Valve
Field-Supplied and
Field- Installed

Right Side

of Liebert XDV

Refer to Table 4 for details.